![DuctlessAire DA-09 Скачать руководство пользователя страница 9](http://html.mh-extra.com/html/ductlessaire/da-09/da-09_service-manual_2537953009.webp)
Service Manual
9
guidelines provided for the Indoor and Outdoor unit.
1.4
Sun Rooms or 4 Season Rooms
Sizing
Sizing and Location of the Mini Split to the room is still
EXTREMELY
IMPORTANT.
DuctlessAire
recommends a 12,000 Btu/h capacity for each 325 to
350 Sq Ft of the Room
.
The throw of the 9 or 12,000 Btu/h units is approximately 15 feet, and the 18 or 24,000
Btu/h units have a throw of approximately 25 feet.
Sun Rooms are a great application for
DuctlessAire
Mini Split units however there are
several items that must be addressed to make the installation a success.
Ambient
Sun Rooms are different in their application as they by definition have a large solar gain
and therefore can require cooling in cold ambient temperatures. Therefore as per
Computer room and Commercial applications it is mandatory to install the ICM 326H low
ambient control and a crankcase heater on the system.
Indoor unit Location
For optimum unit operation the High Wall Indoor unit should be mounted a minimum of 6
feet from the floor. A minimum height of 4 feet must be maintained for correct unit
operation.
Ensure air flow is never directly straight onto areas where people may sit or congregate, as
the temperature difference between Supply and Return air will be approximately 35 DegF.
Heat Pumps
In order to use the Sun Room year round Heat Pumps are the recommended system,
Содержание DA-09