![DuctlessAire DA-09 Скачать руководство пользователя страница 27](http://html.mh-extra.com/html/ductlessaire/da-09/da-09_service-manual_2537953027.webp)
Service Manual
27
3.4
2-Way Valve and 3-Way Valve
The refrigerant line set connections can be found under the GRAY plastic caps not the
brass ones which cover the valve stems.
DO NOT TRY TO PUT THE FLARE NUTS ON THE THREADS FOR THE
SERVICE VALVE STEMS – THEY WILL NOT FIT
Once the line set is connected, the system, it should be pressure tested and then evacuated
to a minimum of 200 Microns, the charge for the system has to be released from the
Outdoor unit.
To do this, it is very important that the
SUCTION SERVICE VALVE MUST BE
OPENED FIRST
This will allow the refrigerant to flood the system without passing through the capillary
tube. If the Liquid service valve is opened first it is possible to log Oil in the capillary
tube, especially if the outdoor temperature is low.
If this happens the unit will drop into a vacuum immediately on start up of the unit, to
repair this either recover the refrigerant charge and start evacuation again or it is possible
to clear the log by driving up the condenser head pressure by blocking off the outdoor coil
or unwiring the condenser fan.
Содержание DA-09
Страница 1: ...Service Manual 1 Service Manual Mini Splits ...
Страница 12: ...Service Manual 12 ...
Страница 13: ...Service Manual 13 ...
Страница 14: ...Service Manual 14 ...