![DuctlessAire DA-09 Скачать руководство пользователя страница 10](http://html.mh-extra.com/html/ductlessaire/da-09/da-09_service-manual_2537953010.webp)
Service Manual
10
however it may be advisable to install some additional source of heat, such as electric
baseboard if the Sun Room is to be used in temperatures below 24 DegF.
Below 24 DegF the air temperature delivered from the unit will be close to body
temperature making it feel uncomfortable, as when the Outdoor temperature falls the
unit capacity and efficiency reduces, together with the unit requiring more frequent defrost
cycles.
This will assist in truly making the Sun Room a room to be enjoyed in comfort all year
round.
1.5
Low Ambient Cooling
As stated in the Computer Room, Commercial and Sun Room application pages -
ALL
DuctlessAire
models are capable of providing
COOLING
operation down to an
ambient temperature of 65 DegF.
Therefore to operate in Cooling down to an ambient temperature of 32 DegF, both an
ICM326H Fan Speed Controller, plus a Crankcase Heater, either a Mars #32342 or
Raychem #CCH-1 or 2 bellyband types
MUST
be installed.
For cooling operation below 32 DegF, and down to a minimum of 0 DegF,
DuctlessAire
recommends that Wind Baffles be installed on both the Coil Inlet and Fan Outlet of the
Outdoor unit. Please contact
DuctlessAire
directly for details of the design requirements
for the Wind Baffles.
We also recommend using these Wind Baffles in applications where the units may be
exposed to prevailing winds blowing though the condenser coils. These winds may cause
the unit to over condense and freeze the indoor unit, or allow liquid refrigerant to be
inadvertently slugged back into the compressor.
Installing the ICM326H Fan Speed Controller
The controller should be located per the instructions provided, it is not weatherproof,
therefore should be mounted inside the compressor compartment of the Outdoor unit.
DuctlessAire
Units have Ball Bearing Condenser Fan motors, set both the Hard Start and
cut out speed setting dials to 1/3 off the
MINIMUM