Service Manual
23
DA-12
115V-1Ph-60Hz
15A
DA-18
208/230V-1Ph-60Hz
20A
DA-24
208/230V-1Ph-60Hz
25A
2.4
Line Set Lengths and Sizes
Ensure that the Maximum Line Set lengths are observed; the System will not operate
correctly and will probably experience premature failure of its components.
DO NOT
upsize or alter the Line Set Sizes from those published, Quietside cannot
guarantee operation with incorrectly sized or extended Line Sets
DO NOT install Sight Glasses or Filter Driers in the Line Set
Model
Suction
Expanded Gas
Total Length
Lift
DA-09
1/2”
1/4”
50ft
20ft
DA-12
1/2”
1/4”
50ft
20ft
DA-18
5/8”
3/8”
50ft
20ft
DA-24
5/8”
3/8”
50ft
20ft
All of the units have the expansion device located in the Outdoor unit; therefore both the
Suction and the “Liquid” line MUST be insulated (separately)
2.5
Indoor Unit Positioning
High Wall units must be mounted high on the wall, use a height of 6 to 8 feet, with nothing
that would restrict airflow in front of the indoor units. This will provide optimum
operation. Minimum height from the floor is 4ft.
The air returned to the indoor unit must be indicative of the true temperature of the entire
space. When the unit is high on the wall, and the discharge air travels along the longest
path possible to return to the unit (no blockage or reflected air returned) the system will