Service Manual
6
365 days 24/7. This means that the Outdoor unit will be exposed to temperature below the
minimum design ambient of 65 DegF
Therefore for cooling below 65 DegF,
DuctlessAire
insists on the following items to be
installed on the system.
1.
ICM 326H Fan Speed controller
2.
Crankcase Heater on ALL units
If winter temperature fall below 32 DegF a Wind Baffle on the Coil Inlet and the
Exhaust of the condenser fan is required.
This will isolate the unit from any wind that could cause the unit to over condense,
slugging liquid refrigerant back to the Compressor, which can damage the valve plate,
wash oil from the bearing services and eventually cause the Compressor to fail.
A Wind Baffle will provide cooling operation down to an Ambient of 0 DegF Wind
Baffles are field fabricated, drawings are available on request from
DuctlessAire
.
1.2
Commercial, Offices, Shops, Churches etc
Sizing
Again Sizing and Location of the Mini Split to the room is
EXTREMELY
IMPORTANT.
DuctlessAire
recommends a 12,000 Btu/h capacity for each 350 to 450 Sq Ft of the
Room
Do not exceed this sizing guideline for the same reason as the computer room
application information
Again
DO NOT
install
DuctlessAire
Mini Splits in rooms of less than 100 Sq Ft
Ambient
Check as to the lowest ambient temperature that will be required for cooling, the minimum
Содержание DA-09