missing phrase for supply voltage. Match right power
supply voltage
is too low.
install voltage regulator.
The main fuse
burn-out.
Replace fuse.
The voltage dependent resistor
has been burst
Change
the
voltage
dependent resistor
This AC can
’
t receive the remote
signal because of receiving head
or window failure
Repair or replace this
receiving head or window
poor contact
for
socket connector
of PCB.
Check. Repair or replace
this PCB.
The transformer damaged.
Replace the transformer.
The PCB damaged and no output. Replace the PCB.
08 Unit
suddenly
doesn’t
work
after
running
some time.
Power failure.
fuse of power supply burn out.
Replace this fuse.
poor contact
for the plug.
Check repair and replace
the plug and socket.
Have set regularly shutdown.
Restart the A/C.
The PCB has any trouble
Repair or replace the PCB