G The remember function during the power failure can only remember the
operation mode, the turbo, economy, and sleep function can not be remembered.
2.
Pre Installation Requirements
2.1
Unit sized correctly and applied correctly
Refer to Pages 3 through 10 for information on the sizing and additional requirements for
the specific application required.
2.2
Electrical Requirements
All the
DuctlessAire
units require Line Voltage interconnect for both power for the
Indoor unit and Control voltage for the Outdoor unit.
There is
NO
24V AC wiring on these units, therefore all the electrical wiring between the
units
MUST
be a minimum of 14 AWG.
The Outdoor unit
MUST
be fed with power from a Breaker and/or Local Disconnect.
The Outdoor unit
MUST
provide power for the Indoor unit.
Do not install local disconnects or J boxes adjacent to the Indoor unit as this can cause
mis-wiring and polarity issues for the system.
2.3
Breaker Size
Check the Breaker Size is correct for the system,
DuctlessAire
units do not have start
components for the compressor, and therefore they rely on the correct power and
amperage supply to start
Unit
Power Supply
Breaker Size
DA-09
115V-1Ph-60Hz
15A