I The “sleep” and “turbo” can not be operated at the same time, that is to say there is
no sleep function during the turbo operation, and there is no turbo function in the
sleep status.
A
nti- mildewing operation function
If the air conditioning is shut down during the cooling operation under the
cooling,dehumidify or automation mode, then the air conditioning will execute the
anti- mildewing operation function. The compressor and indoor blower will be
operated according to the curve in the start up period that is shown in the following
figure, the indoor blower is in the operation status of low wind speed, the air flap
will be closed thirty seconds after it has been operated according to the original
status, the outdoor blower and the four- way valve are in the closing status.
A
:
controlled object
B
: indoor blower
C
:compressor
D
: start up
E
: shut down
F
: time