Service Manual
4
1. Applications and Features
1.1 Computer or Data Server Rooms
Mini-splits are designed to primarily keep people comfortable. That means the typical
range of temperatures for the zone is 70-72 Deg F.
Mini Splits were not specifically designed for cooling server rooms or other data rooms
however due to their size and ease of installation this is a very common application, and
also the #1 Technical Service issue.
But
FOLLOWING
these guidelines can make for a reliable, profitable installation in this
application.
Sizing
Sizing of the Mini Split to the room is
EXTREMELY IMPORTANT
.
DuctlessAire
recommends a 12,000 Btu/h capacity per 200 to 250 Sq Ft of room
size. Do not exceed this sizing guideline.
Installing large capacity systems in small rooms will lead to short cycling of the
compressor as the supply airflow from the unit to “bounces back” into the return air stream
of the unit
If using the larger capacity units, Supply air is discharged at a velocity of approximately
6ft per second.
With a small room, where the opposite wall to the unit is less than 10ft away the supply air
only circulates for approximately 4 seconds before returning to the unit.
The room temperature sensor is located on the surface of the cooling coil, if the supply air
quickly “bounces back” into the unit, it will satisfy the sensor and the compressor will be
cycled off.
All
DuctlessAire
mini splits feature continuous fan operation, maintaining circulation
in the room rapidly picking up the warmer return air from the room, causing the return air
sensor