MicroController Control System
Testing And Adjusting
Component Tests
Battery voltage and high amperage are present.
Injury to personnel is possible. Disconnect the
battery and discharge the head capacitor (HEAD
CAP) before any contact is made with the control
panel.
NOTICE
Do not use steam or solvent to clean the controls.
Damage can be caused to the control panel. Use
pressure from an air hose with a maximum
pressure of 205 kPa (30 psi) to clean the control
panel when necessary. The air supply must be
equipped with a water filter.
NOTE:
When control wires and power cables or bus
bars are to be connected to the same bolt or
stud, place all control wires together on the
top of the bus bar or power cable.
Use the electrical schematic (located inside rear
panel cover) to locate components referred to by
name and number in the procedures that follow.
All wires must be located as shown on the schematic.
Refer to SB4087E00 schematic(A174502) as
attached.
WARNING
Conductor and Switch Continuity
1.
Set the multimeter to the 200
Ω
range.
2.
Use the multimeter to perform the continuity test. lf
continuity exists, the measurement will be less
than 1 ohm. lf the measurement is more than this,
continuity does not exist and the problem will have
to be repaired.