Inclination adjustment
If the superstructure or the ground are
inclined at an
angle of 1% or more
, slope compensation must be
provided.
using Wedges for screw-jack
.....
%
These prefabricated birch plywood wedges make it
possible to stand load-bearing towers in the perpendic-
ular on surfaces with various inclinations, even when
utilising the full leg load.
Inclined superstructures
Securing the superstructure at angles of over 12%:
➤
Connect the head-plate to the longitudinal beam
(e.g. with Locking rod 15.0/33cm and Super-plate
15.0 or Angle anchor plate 12/18)
Inclined ground surface
using Staxo wedge support WS10
Used with timber wedges, this component provides
angle adjustment to floor-slab constructions with a
max. inclination of 45°.
Bolted into the multi-purpose waling or steel waling, this
wedge support prevents the timber wedges from slip-
ping and ensures that the loads are safely transferred.
Note:
If the legs of the load-bearing tower have to be located
outside the pattern of drilled holes in the multi-purpose
waling, then a suitable 20
mm diam. hole must be
drilled in the web of the waling.
CAUTION
Excessively steep wedges may slip away!
➤
Maximum inclination: 20%!
For this reason, wedges must NOT be placed
on top of one another in an attempt to compen-
sate for inclinations that are greater than 20%.
A
Wedge for screw-jack
.....
%
B
Locking rod 15.0/33cm
C
Super-plate 15.0
D
Wedge for screw-jack
.....
%
98024-285-01
A
B
C
D
98024-286-01
NOTICE
This type of connection is no substitute for
extra structural design measures such as
back-stays.
View without
superstructure
a ... min. 15
cm
A
Staxo wedge support WS10
B
Timber wedge, project-specific
C
Multi-purpose waling WS10
Top50
D
Nailed connection
NOTICE
The grain of the timber wedges must always
be in the vertical!
See the type specification sheet 'Load-bearing
tower Staxo 40' for alternative solutions.