User Information
Load-bearing tower Staxo 40
General remarks
61
999805002 - 09/2018
Shoring to the superstructure with
Eurex 60
For transferring
planned horizontal loads
e.g. wind
loads, concrete loads or in custom applications (e.g. on
inclined load-bearing towers or for high load-bearing
capacities).
Permitted load-bearing capacity of Eurex 60
550 (compressive force)*
Used as a plumbing accessory
* 15
kN tensile force at any extension length
30
kN tensile force at any extension length and when anchored with
2 dowels
Fixing to the ground
➤
Anchor the plumbing accessories in such a way as to
resist tensile and compressive forces!
Holes in plumbing strut shoe Eurex 60:
a ... diam. 28
mm
b ... diam. 18
mm (suitable for Doka express anchors)
Anchoring the footplate
The
Doka express anchor
can be re-used many times
over.
Anchored with one dowel (up to 15 kN tensile
force)
Anchored with two dowels (up to 30 kN tensile
force)
CAUTION
➤
The plumbing strut must not be dismounted
until it is certain that there is sufficient stabil-
ity for the load-bearing tower.
Permitted load-bearing
capacity [kN]
Extension length [m]
A
Doka express anchor 16x125mm
B
Doka coil 16mm
3
4
5
6
7
8
9
10
13
14
35
30
25
20
15
10
5
0
11
12
9745-101
Tr717-200-02
a b
b
9745-222-01
A
B
Follow the Fitting Instructions!
Characteristic cube compressive strength of the con-
crete (f
ck,cube,current
):
min. 25
N/mm
2
(C20/25 concrete)
Required safe working load of alternative anchors
for footplates:
▪
R
d
≥ 30.0 kN (F
permissible
≥ 20.0 kN)
in the diam. 18 mm hole
▪
R
d
≥ 43.5 kN (F
permissible
≥ 29.0 kN)
in the diam. 28 mm hole
Follow the manufacturers' applicable fitting instruc-
tions.
NOTICE
▪
One dowel must be positioned between the
lugs of the footplate.
▪
Remove the footplate from the plumbing
strut for this step.
▪
After anchoring the footplate, reinstall the
Plumbing strut Eurex 60 550 at the position
shown.
Characteristic cube compressive strength of the con-
crete (f
ck,cube,current
):
min. 30
N/mm
2
(C25/30 concrete)
Required safe working load of alternative anchors
for footplates:
R
d
≥ 30.0 kN (F
permissible
≥ 20.0 kN)
Follow the manufacturers' applicable fitting instruc-
tions.
9745-222-03