LonWorks Troubleshooting
Network Guide
115
CHAPTER 7
L
ON
W
ORKS
T
ROUBLESHOOTING
You can use this Troubleshooting Guide to help detect and correct issues that you may
encounter.
Table 32: Troubleshooting ECL Device Symptoms
Symptom
Possible Cause
Solution
Device does not com-
municate on the L
ON
-
W
ORKS
MS/TP
network
The device does not
have power / poor-
quality power.
See
Power Supply Requirements for 24V Controllers
Cut or broken wire.
Isolate the location of the break and pull a new cable.
The maximum num-
ber of devices on a
data bus segment has
been exceeded.
Use a repeater to extend the BACnet data bus. See
Absent or incorrect
supply voltage
1. Check if the device is showing the 'Poor Power Quality' status code (for 24V
controllers). See
for a list of fault codes.
2. Check power supply voltage between 24VAC/DC ±15% and 24V COM pins
and ensure that it is within acceptable limits (for 24V controllers).
3. Check for tripped fuse or circuit breaker.
Overloaded power
transformer (for 24V
controllers)
1. Check if the device is showing the 'Poor Power Quality' status code. See
for a list of fault codes.
2. Verify that the transformer used is powerful enough to supply all controllers.
See
Transformer Selection and Determining the Maximum Power Run Length
page 61.
Network not wired
properly
Double check that the wire connections are correct.
Absent or incorrect
network termination
Check the network termination(s).
Too many Allure EC-
Smart-Vue sensors
are providing network
access
Disable the Net to Subnet Port Settings jumpers on all controllers. If communica-
tions are re-established, re-enable only a few Allure EC-Smart-Vue sensors to
have network access.
The STATUS LED is
blinking
The device has auto-
diagnosed a fault con-
dition
See
for a list of fault codes.
Controller is powered
but does not turn on
Fuse has blown (for
24V controllers)
Disconnect the power. Check the fuse integrity. Reconnect the power.
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...