LonWorks Troubleshooting
Network Guide
117
Refer to the controller's Hardware Installation Guide for how to identify and set a controller's
configuration jumpers and switches.
0-10V output, 24VAC
powered actuator is
not moving
Check the polarity of the 24VAC power supply connected to the actuator while
connected to the controller. Reverse the 24VAC wire if necessary.
Wireless devices not
working correctly
Device not associated
to controller
Using the device configuration wizard, check the configuration of the input. Refer
to the controller's device's user guide for more information.
Power discharge
1. Recharge device with light (if solar-powered) or replace battery (if battery-pow-
ered).
2. Ensure sufficient light intensity (200lx for 4 hours/day).
Device too far from the
Wireless Receiver
Reposition the device to be within the range of the Wireless Receiver. For infor-
mation on typical transmission ranges, refer to the Open-to-Wireless™ Solution
Guide.
Configuration problem
With EC gfxProgram, check the configuration of the input; for example, is it
enabled? Refer to the EC gfxProgram User Guide for more information
Table 32: Troubleshooting ECL Device Symptoms
Symptom
Possible Cause
Solution
Table 33: LED Fault Condition Interpretation for ECB Devices
ECB Device LED
Interpretation
Description
Solution
RX LED not blinking
Data is not being received from the
BACnet MS/TP data bus.
If there is no communication, see
.
TX LED not blinking
Data is not being transmitted onto
the BACnet MS/TP data bus.
POWER constant on
Power is available at the device.
However this does not mean that
the quality of supplied power is
good. See
on page
If not lit, see
Power Supply Requirements for 24V Controllers
page 61 for the power requirements.
STATUS blinking
See following table.
-
Table 34: STATUS LED Interpretation for Normal Operation with ECB Devices
Device STATUS LED blink patterns
Status
Description
One fast blink
Initialization
The device is starting up.
Fast blink continuous
:
(150ms On, 150ms Off, continuous)
Firmware upgrade in progress
Controller operation is temporarily unavailable. The
new firmware is being loaded into memory. This takes
a few seconds. Do not interrupt power to the device
during this time.
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...