BACnet MS/TP Communication Data Bus Fundamentals
Network Guide
35
Set the Max Master and Max Info Frames as follows.
1.
Right-click the
Link
node in the
Nav
tree and select
Ms/Tp Configuration
.
2.
The
Configure Ms/Tp devices
dialog box is displayed. The network must be live; the
Sta-
tus
shown in
Configure Ms/Tp devices
window must be
{ok}
.
Figure 20: Setting the Max Master on the Data Bus Master (EC-BOS) to the Highest MAC Address Used
on the BACnet MS/TP Data Bus
3.
A confirmation message is shown.
4.
Set the
Max Info Frames
to 20 for the Data Bus Master (EC-BOS) as shown in the screen
below.