LonWorks Communication Bus Fundamentals
Network Guide
57
In a
bus
topology, the maximum wire length is 1400 meters (4593 feet). The maximum stub
length on a TP/FT 10 channel is 3 meters (10 feet). A stub is a section of unterminated trans-
mission line that branches off the main transmission line of interest. The branch line is termi-
nated as an open circuit.
In a
free
topology, the maximum length is 400 meters (1312 feet) node-to-node and 500
meters (1640 feet) total wire length.
Type 2:
16 AWG (Ø1.3mm), 1 twisted pair (1P), stranded conductor (STR), tinned copper (TNC), PVC
insulation, PVC jacket, unshielded, plenum FT6, CSA 600V or UL 300V.
In
bus
topology, the maximum wire length is 2700 meters (8858 feet). The maximum stub
length on a TP/FT 10 channel is 3 meters (10 feet).
NEC Rating
UL listed art 800 plenum
CSA
Flame rated
Untwisted wires or cables containing flat or parallel untwisted conductors must not
be used on an L
ON
W
ORKS
twisted pair channel. The use of theses wires/cables may
result in improper network operation and could, in certain circumstances, result in
damage to nodes connected to such a channel.
In the event that the limits on the number of transceivers or total wire distance are
exceeded, then one FTT physical layer repeater can be added to interconnect two
segments and double the overall system capability.
Table 13: TP/FT 10 Type 2 Cable Attributes
Parameter
Details
Conductor
Gauge (AWG)
16 AWG (see also
Metric Conversions for Wire Gauge
on page 133).
Conductor
Count
2 Conductors (twisted pair)
Conductor Type
Stranded conductor
Material
Tinned copper
Plenum
Plenum rated
NEC Rating
UL listed art 800 plenum
CSA
Flame rated
Table 12: TP/FT 10 Type 1 Cable Attributes
Parameter
Details
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...