BACnet Troubleshooting
Network Guide
113
Table 30: STATUS LED Fault Condition Interpretation for ECB Devices
The STATUS LED is
always ON (ECB PTU
Series only)
No anomaly
Normal operation.
Table 29: STATUS LED Interpretation for Normal Operation with ECB Devices
Device STATUS LED
blink patterns
Status
Description
Device STATUS LED
blink patterns -
every 2 seconds
(highest priority
shown first)
Possible Cause
Corrective Action
Long Long Long blink
(800ms On, 300ms
Off, 800ms On, 300ms
Off, 800ms On)
Offline
The device has not received a BACnet token, and therefore cannot communicate
on the network: Verify that the controller's MAC Address is unique on the BACnet
MS/TP Data Bus - see
on page 31. Make sure the con-
troller's baud rate is the same as the BACnet MS/TP Data Bus' baud rate (see
Maximum Number of BACnet MS/TP Devices on a Data Bus Segment and Baud
Rate
on page 14). Verify that the Max Master is set high enough to include this
controller's MAC Address (see
Setting the Max Master and Max Info Frames
on
page 34).
Short Short Long blink
(150ms On, 300ms
Off, 150ms On, 300ms
Off, 800 ms On)
Poor-quality power.
The device has
browned-out (for 24V
controllers)
The voltage at the 24VAC/DC and 24VCOM terminals was not at an acceptable
level during power up.
Short Long blink
(150ms On, 300ms
Off)
Invalid MAC address
The device's MAC address is set to zero (0) or is set to an address higher than
the Max Master. See
BACnet MS/TP Data Bus Token-Passing Overview
on page
32.
Table 31: Verify that the Following Recommendations have been Carried Out Before Calling Technical Support
Recommendation
Description
Properly terminate the BACnet MS/
TP data bus
EOL terminations must be enabled / installed at either end of the data bus only. See
Avoid duplicate MAC Addresses
Verify that no device has a duplicate MAC Address by checking the MAC Address DIP switch
settings on all devices on the data bus, including segments connected by a repeater.
If necessary, isolate devices from the data bus to narrow-down the number of devices that
may be at fault.
All devices must be set to the same
baud rate
When all devices are set to AUTO baud rate, at least one device must be set to a baud rate,
usually the data bus master. See
Maximum Number of BACnet MS/TP Devices on a Data
.
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...