110
Network Guide
Device does not com-
municate on the BAC-
net MS/TP network
Absent or incorrect
supply voltage (for
24V controllers)
1. Check if the device is showing the 'Poor- Quality Power' status code (for 24V
controllers). See
for a list of fault codes.
2. Check power supply voltage between 24VAC/DC ±15% and 24V COM pins
and ensure that it is within acceptable limits (for 24V controllers).
3. Check for tripped fuse or circuit breaker.
Overloaded power
transformer (for 24V
controllers)
1. Check if the device is showing the 'Poor- Quality Power' status code. See
for a list of fault codes.
2. Verify that the transformer used is powerful enough to supply all controllers.
See
Transformer Selection and Determining the Maximum Power Run Length
page 43.
Network not wired
properly
Double check that the wire connections are correct.
Absent or incorrect
network termination
Check the network termination(s).
Max Master parameter
Configure the
Max Master
to the highest MAC Address of any device on the MS/
Setting the Max Master and Max Info Frames
There is another con-
troller with the same
MAC Address on the
BACnet MS/TP data
bus
Each controller on a BACnet MS/TP data bus must have a unique MAC Address.
Look at the MAC Address DIP switch on the faceplate of each controller. If it is set
to 0 (all off), use an Allure EC-Smart-Vue sensor to check the MAC Address.
There is another con-
troller with the same
Device ID on the BAC-
net intranetwork
Each controller on a BACnet intranetwork (the entire BACnet BAS network) must
have a unique Device ID. Use an Allure series communicating sensor to check
the Device ID of each controller. See
Adopting a Numbering System for MAC
Addresses, Device Instance Numbers, and Network Numbers
BACnet data bus
polarity is reversed.
Ensure the polarity of the BACnet data bus is always the same on all devices.
See
BACnet MS/TP data bus is polarity sensitive
Cut or broken wire.
Isolate the location of the break and pull a new cable.
The BACnet data bus
has one or more
devices with the same
MAC Address.
See
Adopting a Numbering System for MAC Addresses, Device Instance Num-
The baud rate for all
devices are set to
AUTO
At least one device must be set to a baud rate, usually the data bus master. See
Setting the Baud Rate for ECB-Series Controllers (optional)
The device is set to a
MAC Address in the
range of 128 to 255.
See if the STATUS LED on the device is showing a fault condition. See
for a list of fault codes.
This range is for slave devices that cannot initiate communication. All Distech
Controls' devices are master devices and must their MAC Address set accord-
ingly. See
The maximum num-
ber of devices on a
data bus segment has
been exceeded.
Use a repeater to extend the BACnet data bus. See
MS/TP Devices on a Data Bus Segment and Baud Rate
on page 148.
Table 27: Troubleshooting ECB Device Symptoms
Symptom
Possible Cause
Solution
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...