124
Network Guide
Table 40: Error code Interpretation for Allure EC-Smart-Vue Sensor Symptoms
Device is not communicat-
ing with controller
Is the address correctly set
to a unique address?
Each Allure EC-Smart-Vue sensor must be set to a unique address for
each controller. See
Commissioning a Controller with an Allure EC-
on page 98.
Is the device too far from
controller?
Verify the distance between the device and the controller. See
Is there a configuration
problem?
With EC-
gfx
Program, check the configuration of the sensor, for exam-
ple, is it enabled? Refer to the EC-
gfx
Program User Guide for more
information.
Have the subnetwork EOL
settings been correctly set?
Only the last module on the subnetwork data bus must have its EOL
termination set to ON. See
, and
. When
one or more ECx-400 Series IO Extension modules are connected to
the controller, only the last ECx-400 must have its EOL termination set
to ON. See
Controller cannot communi-
cate on the LONWORKS
network (ECL controllers
only)
Too many Allure EC-Smart-
Vue sensors are providing
network access
Disable the Net to Subnet Port Settings jumpers on all controllers (for
jumper location, see
LAN through an Allure EC-Smart-Vue Sensor for a
on page 104). If communications are re-estab-
lished, re-enable only a few Allure EC-Smart-Vue sensors to have net-
work access.
Allure EC-Smart Vue sen-
sor motion detector window
indicator is always ON
Does the connected con-
troller have Allure EC-
Smart-Vue sensor firmware
that supports the motion
and CO
2
sensor?
When the Allure EC-Smart-Vue sensor is connected to a controller, its
firmware is loaded from the controller. In this case, the controller has an
earlier version of Allure EC-Smart-Vue sensor firmware that does not
support the motion or CO
2
sensor. To upgrade to the latest Allure EC-
Smart-Vue sensor firmware, download the firmware from SmartInstaller
and refer to the firmware upgrade procedure in the EC-
gfx
Program
User Guide.
The Motion or CO
2
output
of the associated ComSen-
sor block always reads
NULL in EC-
gfx
Program
The CO
2
sensor readings
are too high, too low, or
inconsistent between sen-
sors
Immediately after installing
the Allure EC-Smart-Vue
sensor with CO
2
sensors,
are the CO
2
sensor read-
ings incoherent?
If the CO
2
sensor readings seem unusual or show inconsistencies
between sensors in the same building right after installation, the follow-
ing reasons should be taken into consideration:
- Concentration levels in each space may be different
- The installer may have unintentionally blown into the sensor while
installing it.
- The sensor may have been dropped or mishandled during shipment
causing a minor shift in the original factory calibration.
Allow up to 14 days of operation (without power interruptions) for the
sensor to calibrate itself according to its new environment.
Symptom
Possible Cause
Solution
Symptom
Possible Cause
Corrective Action
Clock icon flashing for 15
seconds
Cannot communicate with
controller.
Wait for the communication link to the controller to be established.
Verify wiring.
Verify that all Allure EC-Smart-Vue sensor's Subnet IDs are unique for
this controller. See
Setting the Allure EC-Smart-Vue Sensor's Subnet
on page 98.
After 15 seconds: Error
code 1 with Bell icon
Error code 2 with Bell icon
Invalid configuration.
In EC-
gfx
Program, resynchronize the code with the controller.
Contact Distech Controls customer support.
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...