BACnet MS/TP Communication Data Bus Fundamentals
Network Guide
37
An example of this numbering system is shown below.
Figure 22: BACnet MS/TP Numbering System for MAC Addresses, Device Instance Numbers, and Network
Numbers
Table 8: Recommended Numbering Scheme for MAC Addresses, Instance Numbers, and Network
Numbers
Description
Range
Example
BACnet/IP Network Number
0 to 65 534
1
Building Controller BACnet/IP Device
Instance Numbers: Multiples of 10 000
10 000 to 4 190 000
10 000
20 000
BACnet MS/TP Network Number: Building
Controller BACnet/IP Device Instance Num-
ber/1000 + 0,1,2,3,4 (for each LAN)
10 to 4190
10
11
12
BACnet MS/TP Device Instance Number =
EC-BOS BACnet MS/TP Network Number *
1000 + MAC Address
10 000 to 4 190 256
10 006 where MAC
= 6
When discovering devices with an EC-BOS which has the routing option config-
ured, it will discover all BACnet devices connected to all EC-BOS controllers. Make
sure to add only the devices connected to the MS/TP port of the specific EC-BOS
being configured. Using this numbering system will greatly help to identify those
devices that should be added to a given EC-BOS.
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...