Subnetwork Installation Guidelines
Network Guide
95
For more information about 2-Wire subnetwork data bus grounding, see:
•
ECx-4XX I/O Extension Module Power Supply Requirements
on page 47 for ECB-600
controllers.
•
ECx-4XX I/O Extension Module Power Supply Requirements
on page 66 for ECL-600
controllers.
ECx-4XX I/O Extension Module Addressing
Each ECx-4XX I/O Extension Module on a 2-Wire subnetwork data bus needs to be set to a
unique address. The address is set through the DIP switch located on the ECx-4XX I/O Exten-
sion Module's faceplate. The range of valid addresses is 1 to 7.
An example of how to set an ECx-4XX I/O Extension Module address DIP switch is shown
below.
Table 25: ECx-4XX I/O Extension Module Address DIP Switch Settings
Switch Position
Value
1
2
4
OFF
OFF
OFF
Invalid
ON
OFF
OFF
1
OFF
ON
OFF
2
ON
ON
OFF
3
OFF
OFF
ON
4
ON
OFF
ON
5
OFF
ON
ON
6
ON
ON
ON
7