112
Network Guide
Refer to the controller's Hardware Installation Guide for how to identify and set a controller's
configuration jumpers and switches.
Wireless devices not
working correctly
Device not associated
to controller
Using the device configuration wizard, check the configuration of the input. Refer
to the controller's device's user guide for more information.
Power discharge
1. Recharge device with light (if solar-powered) or replace battery (if battery-pow-
ered).
2. Ensure sufficient light intensity (200lx for 4 hours/day).
Device too far from the
Wireless Receiver
Reposition the device to be within the range of the Wireless Receiver. For infor-
mation on typical transmission ranges, refer to the Open-to-Wireless™ Solution
Guide.
Configuration problem
With EC-
gfx
Program, check the configuration of the input; for example, is it
enabled? Refer to the EC-
gfx
Program User Guide for more information
Table 27: Troubleshooting ECB Device Symptoms
Symptom
Possible Cause
Solution
Table 28: LED Fault Condition Interpretation for ECB Devices
ECB Device LED
Interpretation
Description
Solution
RX LED not blinking
Data is not being received from the BACnet
MS/TP data bus.
If there is no communication, See
TX LED not blinking
Data is not being transmitted onto the BACnet
MS/TP data bus.
POWER constant on
Power is available at the device. However this
does not mean that the quality of supplied
power is good. See
on page 41.
If not lit, see See
Power Supply Requirements for 24V
on page 41 for the power requirements.
STATUS blinking
See following table.
-
Table 29: STATUS LED Interpretation for Normal Operation with ECB Devices
Device STATUS LED
blink patterns
Status
Description
One fast blink
Initialization
The device is starting up.
Fast blink continuous:
(150ms On, 150ms
Off, continuous)
Firmware upgrade in progress
Controller operation is temporarily unavailable. The new
firmware is being loaded into memory. This takes a few
seconds. Do not interrupt power to the device during this
time.
The STATUS LED is
always OFF (Not
applicable to
ECB-PTU Series)
No anomaly
Normal operation.
Содержание ECB-VAV
Страница 1: ...User Guide Network Guide...
Страница 6: ...Table of Contents 4 Network Guide...
Страница 52: ...50 Network Guide...
Страница 70: ...68 Network Guide...
Страница 110: ...108 Network Guide...
Страница 121: ...LonWorks Troubleshooting Network Guide 119...
Страница 122: ...120 Network Guide...
Страница 124: ...122 Network Guide...
Страница 128: ...126 Network Guide...
Страница 134: ...132 Network Guide Figure 75 Example of How to Set a DIP Switch to 82 ON B A For example 82 A 1010 B 010...
Страница 136: ...134 Network Guide...
Страница 137: ...Network Guide...
Страница 138: ...Network Guide_UG_24_EN...