17 24 Hour Emergency
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
18 24 Hour Sprinkler
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
19 24 Hour Water
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
20 24 Hour Freeze
is similar to 24 Hour Burglary except for System Event output type and SIA identifier.
21 24 Hour Latching Tamper.
This zone type, when violated, will cause arming of the system (both partitions)
to be inhibited until the valid Installer code is entered. If this zone type is violated, the Installers code
must be entered ([*][8] Installers Code) before the system can be armed.
22
Momentary Keyswitch Arm.
A keyswitch module may be connected to the zone programmed as
Momentary Keyswitch arm. Momentary activation of this zone will alternatively arm and disarm the
system and silence alarms. Note that the keypad will not display an indication when this type of zone is
activated.
23 Maintained Keyswitch Arm.
A Normally Open Keyswitch module may be connected to the zone
programmed as Maintained Keyswitch arm. In the restored state, the panel is disarmed. Any violation of
the zone will cause the system to arm (Alarm, Tamper, Fault).
24-26 Not Used
87
Delayed 24 Hour Fire (Wireless)
works the same way as the Standard fire zone, except the alarm
memory and transmission by the communicator is delayed by 30 seconds. If the alarm is acknowledged
by pressing any key within 30 seconds, the bells will silence and the transmission will be aborted. If after
the alarm has been acknowledged, and the smoke detector has not been restored to normal, after 90
seconds the bell output will be activated again, in which the user then has another 30 second delay before
the bell output latches and communications is activated. A code would then be required to silence the bell
output.
Note: The Fire Delay will be terminated if a 2nd Fire zone is tripped or if the [F] key is pressed during a
delay.
88
Standard 24 Hour Fire (Wireless)
is a fire zone that is specially used for pull station type circuits. On
alarm, the bell output will sound to indicate that the fire loop has been activated. If enabled, the
communicator will immediately transmit the alarm to the monitoring station.
Note: For all Fire type zones the Zone Attributes should not be changed from the default
settings.
8.2.2 System Times [005]
This section requires 4 three digit entries.
Note: Entry of 000 in these sections will result in 255 second times.
Entry Delay 1: (001-255) Seconds
This value determines the Entry delay time for Delay 1 type zones. The default Entry
Delay 1 time is 30 seconds.
Entry Delay 2: (001-255) Seconds
This value determines the Entry delay time for Delay 2 type zones. The default Entry
Delay 2 time is 45 seconds.
Exit Delay:
(001-255) Seconds