Digital Security Controls Ltd.
17
Private and Confidential
Installation Manual
DATE : 09/30/97
DRAFT
only the Trouble LED will be on.
OFF = Tampers and Faults Annunciate as Open
The panel will annunciate the respective Zone if the zone is in the Tamper or Fault states.
The Trouble LED will also be lit.
[5] Not Used
[6] Audible Exit Fault Option
ON = Audible Exit Fault is Enabled.
If a non force-armable Delay 1 or Delay 2 type zone is left open at the end of the Exit Delay, the
Entry Delay will begin immediately and the bell or siren will sound a steady alarm for the time
programmed as Bell Timeout. This feature is designed to immediately alert the user that their
system has been armed incorrectly.
OFF = Audible Exit Fault is Disabled.
Note: For [*][9] arming, if Audible Exit Fault is enabled a violated zone will begin entry delay as
per Audible Exit Fault functionality. If this option is disabled, a violated delay zone at the end of
the exit delay will cause an instant alarm.
[7] Event Buffer Swinger Options
ON = Event Buffer Follows Swinger Shutdown.
Once an event reaches its Swinger Shutdown limit programmed in Section [370], it will no longer
log to the Event Buffer until the Swinger Shutdown is reset. This avoids filling the Event Buffer
with useless events.
OFF = Event Buffer Logs Events past Swinger Shutdown.
[8] Fire Signaling Options
ON = Temporal
Three Fire Signal.
In order to comply fully with NFPA 72, all Fire Bells will sound in the Temporal Three Pattern as
described in the NFPA standard if this option is enabled. This cadence is as follows: 500ms ON,
500ms OFF, 500ms ON, 500ms OFF, 500ms ON, 1.5 s OFF.
OFF = Standard Pulsed Fire Signal.
All fire bells will sound with the standard 1 second on/1 second off fire bell cadence.
[014] Second System Options Code
[1] Bell Squawk Options
ON = Arm / Disarm Bell Squawk Enabled.
The Bell output will sound a single squawk when armed in any manner, incl Auto-arm, and a
double squawk upon disarming the system. If there are alarms in memory, the bell will emit a series
of three squawk pairs to indicate the alarm memory.
OFF = Arm / Disarm Bell Squawk Disabled.
The Bell output will not squawk when the system is armed or disarmed in any manner.
[2] Bell During Auto-Arm Options
ON = Bell Squawk During Auto-Arm Enabled.
The Bell output will sound a single squawk every 10 seconds during the 1 minute Auto-Arm Pre-
alert time.
OFF = Bell Squawk During Auto-Arm Disabled.
The Bell output will not be activated during the 1-minute Auto-Arm warning time.
[3] Bell Squawk On Exit Options
ON = Bell Squawk On Exit Delay.
The Bell output will squawk once per second during the Exit Delay time. The bell will also sound
3 squawks per second for the final 10 seconds.
OFF = No Bell Squawk On Exit Delay.
Note: This audible option applies to ALL manual arming modes (Stay, Away, No Entry, etc)