background image

Digital Security Controls Ltd.

                  

32

                                               Private and Confidential

Installation Manual

DATE :  09/30/97

DRAFT

8.2.14 Communicator Option Codes

[380]  First Communicator Options Code

[1]  Communications Options

ON = Communicator Enabled.

The system’s communicator will be enabled and all events with reporting codes will be reported to
the monitoring station.  Refer to the Telephone Number, Reporting Code and Call Direction
Programming Sections.

OFF = Communicator Disabled.

The system’s communicator will be shut off and events will not be transmitted to the monitoring
station.  Downloading may still be performed if enabled.

[2]  Restoral Transmission Options

ON = Restoral Transmissions on Bell-Time-out.

Zone restoral reporting codes will not be transmitted until the zone has been restored 

and

 the Bell

cut-off time has expired.  If the zone is not restored when the bell cut-off time expires, the restoral
will be transmitted when the zone physically restores or when the system is disarmed.  Note that 24
Hour zones will not restore until the zone is physically restored.

OFF = Restoral Transmissions Follow Zones.

Zone restoral reporting codes will be transmitted when the zone is physically restored.  If the
zones are still active when the system is disarmed, the restoral codes will be transmitted when the
system is disarmed.  Note that 24 Hour zones will not restore until the zone is physically restored.

[3]  Dialing Format Options

ON = Pulse Dialing.

The WLS9000 will dial telephone numbers using pulse (rotary) dialing.

OFF = DTMF Dialing.

The WLS9000 will dial telephone numbers using DTMF (dual tone multi-frequency) dialing.

[4]  DTMF Crossover Options

ON = Switch to Pulse Dialing after 4 DTMF attempts.

If DTMF dialing is enabled, the WLS9000 will dial telephone numbers using DTMF dialing for
the first 4 attempts.  If unsuccessful, the system will switch to pulse (rotary) dialing for the final 4
attempts.

OFF = DTMF Dial for all Attempts.

If DTMF dialing is enabled, the WLS9000 will dial telephone numbers using DTMF dialing for all
dialing attempts.

[5]  3rd Phone Number Enabled / Disable

ON = 3rd Phone Number Enabled.

The 3rd Phone number will be used for Alternate Dialing with the 1st Phone Number or as a Backup
of the 1st Phone Number (see light 6).

OFF = 3rd Phone Number Disabled.

The 3rd Phone number will not be used.

[6]  3rd Phone Number Options

ON = Alternate Dialing Enabled (1st & 3rd).

After each dialing attempt, the communicator switches between the 1st Phone Number and 3rd
Phone Number until 8 attempts have been made to each number.

OFF = Call 1st Number, Backup to 3rd Number.

If 8 attempts to communicate to the First Telephone Number fail, up to 8 attempts will be made to
communicate to the Third Telephone Number. If all 8 attempts to communicate to the Third
Telephone Number fail, a Failure to Communicate Trouble will be generated.

Содержание WLS9000

Страница 1: ...ireless Alarm System DRAFT Manual Revision 0 01 Sept 30th 1999 WARNING THIS DOCUMENT IS THE PRIVATE PROPERTY OF DIGITAL SECURITY CONTROLS LTD IT CONTAINS CONFIDENTIAL INFORMATION AND IS NOT TO BE COPI...

Страница 2: ...Selection 9 5 2 4 Voice Prompting 9 5 2 5 Volume of Annunciation 9 5 2 7 Verbal Chime 10 5 2 8 Verbal Alarm 10 5 2 9 Function Keys While in Installer s Programming 11 5 2 10 Memo Feature 11 5 2 11 Rec...

Страница 3: ...ESCORT Programming 39 000 Function Key Programming 39 8 2 17 Special Installer Functions 41 4 USER STAR FUNCTIONS 42 9 0 DOWNLOADING SUPPORT 48 9 1 Downloading Software Version Support 48 9 2 New Pro...

Страница 4: ...ce Prompt User Interface with Help and Status Piezo Alarm to Annunciate Alarm Conditions Eight Programmable Function Keys Hardwired Remote Sounder Support 32 Wireless Zone Support Included in this kit...

Страница 5: ...p via local Blue Lite s Telout Monitoring of the two hardwired zone loops Phone Line Energy Detect Time Keeping in Sleep Mode 4 4 Voice Prompting Components The WLS9000 contains the equivalent of an E...

Страница 6: ...in parallel Two terminals for two Hardwired EOL Zone Loops The common is shared with the Remote Sounder Interface PC LINK Header for Local Downloading Four Terminals for the Telco Interface Tip Ring...

Страница 7: ...llow wireless initiation of Status Status is function key definition 27 and will use Mode Request 1C Volume Control A new function key has been created to allow easy volume control of the voice prompt...

Страница 8: ...ound in the Wizard Flowchart provided by Marketing Hardwired Zone Enrolling The Wizard can also be used to enroll Hardwired zones Serial Numbers X00001 and X00002 have been reserved for the two on boa...

Страница 9: ...sting placed zones As each device receives three Good placements it is removed from the annunciation list and it s corresponding bit in Section 202 205 is toggled to enable the zone on the system Afte...

Страница 10: ...goes into alarm with this feature is enabled the WLS9000 will sound the alarm condition via the high volume piezo but every 5 seconds as programmed for Alarm Tone Period Section 807 Subsection 030 vi...

Страница 11: ...or disarmed can record a memo via the Memo Record function key To record a memo press and hold the Memo Record key for two seconds After the acknowledgement beeps speak the desired message in the dire...

Страница 12: ...s while disarmed ACCESS CODE REQUIRED TO CANCEL AUTO ARMING An access code must be entered to cancel postpone the Auto Arm sequence during the 1 minute Auto Arm Warning time HARDWIRED ZONE LOOP RESPON...

Страница 13: ...f both or either have them have the Transmission Delay Attribute enabled then the transmission of the Cross Zone Police Code should be delayed for the appropriate time programmed If neither of the two...

Страница 14: ...one type will be bypassed If the 1 command is used to activate all Stay Away type zones this zone will have the standard exit delay Once armed this zone will act like an Interior type zone 04 06 Delay...

Страница 15: ...Used 87 Delayed 24 Hour Fire Wireless works the same way as the Standard fire zone except the alarm memory and transmission by the communicator is delayed by 30 seconds If the alarm is acknowledged b...

Страница 16: ...t Options 012 This section determines how the keypad lockout function operates Number of Invalid Codes Before Lockout Program a number from 000 to 255 to determine the number of invalid master duress...

Страница 17: ...ger Shutdown 8 Fire Signaling Options ON Temporal Three Fire Signal In order to comply fully with NFPA 72 all Fire Bells will sound in the Temporal Three Pattern as described in the NFPA standard if t...

Страница 18: ...ated with the exit delay will be silenced when the Exit Delay is terminated Force Armable Delay 1 type zones will also terminate the exit delay OFF Exit Delay Termination Disabled The Exit Delay timer...

Страница 19: ...r entering the 1 Bypass Zones Command an access code must be entered before zones may be bypassed OFF Access Code Not Required to Bypass Zones Enter the 1 Bypass Zones Command to bypass zones Note thi...

Страница 20: ...e ON only while the system is disarmed to indicate that there are bypassed zones on the system When the system is armed the Bypass light will be OFF Note The Bypass status LED will be ON if there are...

Страница 21: ...Subsections 71 and 72 xi This section determines which zone number corresponds to the Hardwired zones found on the main unit Enter the 2 digit zone number to be designated for each loop Please note t...

Страница 22: ...can follow Swinger Shutdown if programmed OFF Swinger Shutdown disabled 7 Transmission Delay Options ON The reporting of zone alarms will be delayed for the programmed time If a valid access code is...

Страница 23: ...ecification requirements the panel will not attempt to communicate if no phone number is programmed This applies to Phone Numbers 1 and 2 310 Telephone Number 1 3 Account Code This is the Account Code...

Страница 24: ...hese access codes will result in transmission of the corresponding reporting code These reporting codes are sent to the Opening and Closing call direction group of the System See also Duress Alarm Rep...

Страница 25: ...ed from the trouble condition These reporting codes are sent to the System Maintenance Call Direction Group Failure to Communicate Phone Numbers 1 2 When events fail to communicate to either telephone...

Страница 26: ...e transmitted to the System Maintenance Call Direction group 8 2 11 Communicator Format Options 360 This section requires 2 two digit entries 1 per phone number The 3rd telephone number uses the forma...

Страница 27: ...ot the Contact I D format will transmit Automatic or Programmed reporting codes please see Section 381 Option 7 Contact I D behaves similarly to SIA with respect to reporting codes if 00 is programmed...

Страница 28: ...1 Smoke FIRE SMOKE DETECTOR 112 Combustion FIRE COMBUSTION 113 Water Flow FIRE WATER FLOW 114 Heat FIRE HEAT SENSOR 115 Pull Station FIRE PULL STATION 116 Duct FIRE DUCT STATION 117 Flame FIRE FLAME S...

Страница 29: ...Failure TROUBLE EXP MODULE FAIL 334 Repeater Failure TROUBLE REPEATER FAILURE 335 Local Printer Paper Out TROUBLE PRINTER PAPER OUT 336 Local Printer FailureTROUBLE LOCAL PRINTER Communication Troubl...

Страница 30: ...T PERIODIC restore not applicable 6A3 Periodic RF xmission TEST PERIODIC RADIO restore not applicable 6A4 Fire test TEST FIRE TEST restore not applicable 6A5 Status report to follow TEST STATUS FOLLOW...

Страница 31: ...10 second interval required before a Telephone Line trouble is generated is programmed here Valid entries are 000 255 for trouble annunciation and transmission LINKS delays of 10 to 2550 Seconds 42 5...

Страница 32: ...med Note that 24 Hour zones will not restore until the zone is physically restored 3 Dialing Format Options ON Pulse Dialing The WLS9000 will dial telephone numbers using pulse rotary dialing OFF DTMF...

Страница 33: ...ns Code 1 Opening After Alarm Keypad Ringback Options ON Opening After Alarm Keypad Ringback Enabled When the Opening After Alarm reporting code is successfully transmitted to a programmed telephone n...

Страница 34: ...n the next communication on Phone Number 2 via L Block to the central station OFF Talk Listen PC5928 on Phone 2 Disabled The panel will not request a Talk Listen session for an event even if the PC592...

Страница 35: ...mmunicated the Event Buffer 75 Full event to central station the panel will call the Downloading Computer s telephone number DLS software will then perform an event buffer upload upon successful conne...

Страница 36: ...internal crystal can be used to keep the most accurate timebase OFF The timebase is the AC power input The 50 or 60 Hz AC power input is normally very stable and can be used as the timebase 3 Arming I...

Страница 37: ...attery at the DSC standard rate of approximately 350 mA 8 For Future Use 702 Second International Options Code 1 Pulse Dial Options ON Pulse Dialing Make Break Ratio is 33 67 OFF Pulse Dialing Make Br...

Страница 38: ...the panel will go off hook search for dialtone for 5 seconds hang up for 20 seconds go off hook search for dialtone for 5 seconds then dial If there is no initial handshake recognized within 40 secon...

Страница 39: ...ons available for the Function Keys If enabled the function key must be held for 2 seconds in order to perform the described function 00 Null Key Not Used The key is not used and will not perform any...

Страница 40: ...ns Pressing this key is the equivalent of entering 6 An access code will be required before entry to this section is allowed to the User Functions menu This key only works while the system is disarmed...

Страница 41: ...eral System Trouble is generated at the keypad This trouble can only be cleared by re entering the Module Placement Test and testing the un enrolled devices Zones can be disabled via Section 202 205 b...

Страница 42: ...tected area Also damaged wiring or contacts on a zone may be temporarily bypassed until repairs can be made so that the panel can be armed To bypass zones enter 1 An access code may be required in ord...

Страница 43: ...ecks setting of 003 will result in 6 checks etc The actual display can be delayed via Installer s Programming This additional check denomination may fluctuate from board to board as it is dependant on...

Страница 44: ...ON OFF COMMAND 4 When Armed Disarmed The Door Chime feature is used to sound a tone from the keypad whenever a zone programmed as a Chime type is activated When the Door Chime feature is turned ON the...

Страница 45: ...d to determine whether an access code should generate an arming disarming Bell Squawk upon entry of the code This is so that Wireless Keys with Access Codes associated with them may generate Arming Di...

Страница 46: ...valid access code during the 1 minute warning period When the code has been entered the warning will be silenced and Auto Arming will be canceled Auto Arming will be attempted at the same time the nex...

Страница 47: ...pass from zones that have been automatically bypassed with the 9 command Note Delay Stay Away and Interior Delay Zones will still have Entry Delay on a 9 armed panel QUICK EXIT 0 When Armed Entering 0...

Страница 48: ...not be implemented unless absolutely necessary 9 2 New Product Support and Structure The DLS files must be rearranged and to accommodate all new aspects of the WLS9000 These files must also remain rel...

Страница 49: ...Zone 7 03 I___II___I Zone 4 04 I___II___I Zone 8 002 ZONE 9 16 DEFINITIONS Default Default 00 I___II___I Zone 9 00 I___II___I Zone 13 00 I___II___I Zone 10 00 I___II___I Zone 14 00 I___II___I Zone 11...

Страница 50: ...I___I Option 4 Bell Squawk On Entry Delay No Bell Squawk On Entry Delay OFF I___I Option 5 Bell Squawk on Trouble No Bell Squawk on Trouble ON I___I Option 6 Audible Exit With Urgency Silent Exit Dela...

Страница 51: ...2 On On On On Off On Off On 03 Instant On On On On Off On Off On 04 Interior On On Off On Off On Off On 05 Interior Stay Away On On Off On On On Off On 06 Delay Stay Away On On Off On On On Off On 07...

Страница 52: ...I I____I I____I I____I 114 ZONE 14 I____I I____I I____I I____I I____I I____I I____I I____I 115 ZONE 15 I____I I____I I____I I____I I____I I____I I____I I____I 116 ZONE 16 I____I I____I I____I I____I I...

Страница 53: ...s Disabled OFF I___I Option 5 Zone 13 is Enabled Zone 13 is Disabled OFF I___I Option 6 Zone 14 is Enabled Zone 14 is Disabled OFF I___I Option 7 Zone 15 is Enabled Zone 15 is Disabled OFF I___I Optio...

Страница 54: ...I___II___I Zone 9 Alarm I___II___I Zone 13 Alarm I___II___I Zone 10 Alarm I___II___I Zone 14 Alarm I___II___I Zone 11 Alarm I___II___I Zone 15 Alarm I___II___I Zone 12 Alarm I___II___I Zone 16 Alarm 3...

Страница 55: ...nic Restoral I___II___I Not Used I___II___I Not Used 330 TAMPER REPORTING CODES ZONES 1 8 I___II___I Zone 1 Tamper I___II___I Zone 5 Tamper I___II___I Zone 2 Tamper I___II___I Zone 6 Tamper I___II___I...

Страница 56: ..._II___I Closing by Access Code 6 I___II___I Closing by Access Code 3 I___II___I Closing by Access Code 7 I___II___I Closing by Access Code 4 I___II___I Closing by Access Code 8 340 CLOSING ARMING REPO...

Страница 57: ..._I Opening by Access Code 27 I___II___I Opening by Access Code 31 I___II___I Opening by Access Code 28 I___II___I Opening by Access Code 32 348 MISCELLANEOUS OPENING DISARMING REPORTING CODES I___II__...

Страница 58: ...MAINTENANCE ALARM RESTORE COMMUNICATOR CALL DIRECTIONS Default Option ON Option OFF ON I___I Option 1 1st Telephone Number Disabled OFF I___I Option 2 2nd Telephone Number Disabled OFF I___I Option 3...

Страница 59: ...Codes OFF I___I Option 4 Closing Confirmation Enabled Closing Confirmation Disabled ON I___I Option 5 Talk Listen on Phone 1 3 Enabled Talk Listen on Phone 1 3 Disabled OFF I___I Option 6 Talk Listen...

Страница 60: ...I___I Option 6 Busy Tone Detection Enabled Busy Tone Detection Disabled OFF I___I Option 7 High Current Battery Charge Standard Current Battery Charge OFF I___I Option 8 For Future Use 702 SECOND INT...

Страница 61: ...Number 01 Main Unit 02 Remote Sounder 00 Not Used Default 00 I___II___I Zone 17 Port Assignment 00 I___II___I Zone 18 Port Assignment 00 I___II___I Zone 19 Port Assignment 00 I___II___I Zone 20 Port...

Страница 62: ..._II___I 4 Key 15 I___II___I 5 Key 06 I___II___I 6 Key 07 I___II___I 7 Key 00 I___II___I 8 Key 17 I___II___I 9 Key 00 I___II___I 0 Key 17 I___II___I Key 11 I___II___I Key 54 Fifth Audio Control Option...

Страница 63: ...I___II___II___I 12 Zone 12 Serial Number 000000 I___II___II___II___II___II___I 13 Zone 13 Serial Number 000000 I___II___II___II___II___II___I 14 Zone 14 Serial Number 000000 I___II___II___II___II___II...

Страница 64: ...ey 06 Serial Number 000000 I___II___II___II___II___II___I 47 Wireless Key 07 Serial Number 000000 I___II___II___II___II___II___I 48 Wireless Key 08 Serial Number 000000 I___II___II___II___II___II___I...

Страница 65: ...NO NO 16 0 Quick Exit YES YES 17 1 Activate Stay Aways YES YES 18 Identified Voice Prompted Help Not Used NO NO 19 Command Output 3 7 3 YES YES 20 Pendant Test Not Used NO NO 21 Command Output 4 7 4 Y...

Страница 66: ...ERVISION OPTIONS 9 16 Default Option ON Option OFF ON I___I Option 1 Zone 09 Supervision Enabled Zone 09 Superv Disabled ON I___I Option 2 Zone 10 Supervision Enabled Zone 10 Superv Disabled ON I___I...

Страница 67: ...y 02 is Disabled Key 02 is Enabled OFF I___I Option 3 Wireless Key 03 is Disabled Key 03 is Enabled OFF I___I Option 4 Wireless Key 04 is Disabled Key 04 is Enabled OFF I___I Option 5 Wireless Key 05...

Страница 68: ...04 Away Arm 05 9 No Entry Arm 06 4 Chime On Off 07 6 4 System Test 08 1 Bypass Mode 09 2 Trouble Display 10 3 Alarm Memory 11 5 User Programming 12 6 User Functions 13 Not Used 14 Not Used 15 Not Use...

Страница 69: ...isabled ON I___I Option 03 FOR ALARM MEMORY Prompt enabled Prompt disabled ON I___I Option 04 FOR DOOR CHIME CONTROL Prompt enab Prompt disabled OFF I___I Option 05 Not Used ON I___I Option 06 FOR SPE...

Страница 70: ..._ Zone 14 615 ZONE 15 LABEL _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Zone 15 616 ZONE 16 LABEL _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Zone 16 617 ZONE 17 LABEL _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ Zone 17 618...

Страница 71: ...the recording an annunciate the label Playback can be pressed several times to re annunciate the Label recording Note Even if Function Keys 7 and 8 have been reprogrammed they will still retain the s...

Страница 72: ...PERATURE 029 BUILDING 091 GARBAGE 153 OUTPUT 215 TIME 030 CABINET 092 GAS 154 OVER 216 TOOL 031 CAFETERIA 093 GATE 155 OVERFLOW 217 TOP 032 CAMERA 094 GIRLS 156 OVERHEAD 218 TRACK 033 CASH 095 GLASSBR...

Страница 73: ...BYPASSING INVALID PREVIOUS TUESDAY BEEN IS PROGRESS THURSDAY BUSY ITEMS P M THIS BABY INTRUSION PARTITIONS TEST CALL ITH PLEASE TWENTY FOUR HOUR CHANGE INCREASE PROGRAMMING TRY CHIME INPUT PROGRAMMED...

Страница 74: ...LACEMENT TEST 990 Installer s Code 990 INSTALLER LOCKOUT ENABLE ENTER 990 INSTALLER S CODE 990 991 Installer s Code 991 INSTALLER LOCKOUT DISABLE ENTER 991 INSTALLER S CODE 991 992 Installer s Code 99...

Страница 75: ...eless Bit OFF to Not Used xiv 1 01 Section 8 2 18 Added function key programming xv 1 01 Section 8 2 17 Exchanged Sections 992 and 999 999 now defaults all 992 defaults the Controller xvi 1 01 Section...

Отзывы: