Digital Security Controls Ltd.
28
Private and Confidential
Installation Manual
DATE : 09/30/97
DRAFT
Sounder / Relay
System Peripheral
Communications
6XX = Test / Misc.
Tests
GG
= Group Number. This 2 digit number is applied when using split arming / disarming function.
CCC
= 3 digit Zone Number or User ID for Opening or Closing. When system status is sent, the CCC
field is defaulted to “000”
P
= Check Sum
Add all 15 digits. If less than 15, complement and send. If greater than 15, repeatedly
subtract 15 until it is less then complement and send. (all 0’s = A’s)
Zone Alarms and Restorals can be programmed to send different messages to the monitoring station. For example, if the
reporting code for zone 5 is programmed with “34”, the monitoring station will receive the following message;
“*BURG* - ENTRY/EXIT - 5“ where 5 is the number of the zone which has been activated.
Different messages to be sent to the monitoring station are:
•
EVENT CODES (as per ADEMCO)
Event code
Message as seen on receiver
Medical Alarms
1AA
Medical
*EMERG* - PERSONAL EMERGENCY - #
1A1
Pendant Transmitter
*EMERG* - PERSONAL EMERGENCY - #
1A2
Fail to Report In
*EMERG* - FAIL TO CHECK IN- #
Fire Alarms
11A
Fire Alarm
*FIRE* - FIRE ALARM - #
111
Smoke
*FIRE* - SMOKE DETECTOR - #
112
Combustion
*FIRE* - COMBUSTION - #
113
Water Flow
*FIRE* - WATER FLOW - #
114
Heat
*FIRE* - HEAT SENSOR - #
115
Pull Station
*FIRE* - PULL STATION - #
116
Duct
*FIRE* - DUCT STATION - #
117
Flame
*FIRE* - FLAME SENSOR - #
118
Near Alarm
*FIRE* - NEAR ALARM - #
Panic Alarms
12A
Panic
*PANIC* - PANIC - #
121
Duress
*PANIC* - DURESS - #
122
Silent
*PANIC* - SILENT PANIC - #
123
Audible
*PANIC* - AUDIBLE PANIC - #
Burglar Alarms
13A
Burglary
*BURG* - BURGLARY - #
131
Perimeter
*BURG* - PERIMETER - #
132
Interior
*BURG* - INTERIOR - #
133
24 Hour
*BURG* - 24 HOUR - #
134
Entry / Exit
*BURG* - ENTRY / EXIT - #
135
Day / Night
*BURG* - DAY / NIGHT - #
136
Outdoor
*BURG* - OUTDOOR - #
137
Tamper
*BURG* - TAMPER - #
138
Near Alarm
*BURG* - NEAR ALARM - #
General Alarms
14A
General Alarm
*ALARM* - GENERAL ALARM - #
143
Expansion module failure
*ALARM* - EXP. MODULE FAIL - #
144
Sensor tamper
*ALARM* - SENSOR TAMPER - #
145
Module Tamper
*ALARM* -
24 Hour Non-Burglary
15A
24 Hour non-Burg
*ALARM* - 24 HR. NON-BURG - #
151
Gas detected
*ALARM* - GAS DETECTED - #
152
Refrigeration
*ALARM* - REFRIGERATION - #
153
Loss of Heat
*ALARM* - HEATING SYSTEM - #
154
Water Leakage
*ALARM* - WATER LEAKAGE - #
155
Foil Break
*ALARM* - FOIL BREAK - #
156
Day Trouble
*ALARM* - DAY ZONE - #
157
Low bottled Gas level
*ALARM* - LOW GAS LEVEL - #
158
High Temp
*ALARM* - HIGH TEMPERATURE - #
159
Low Temp
*ALARM* - LOW TEMPERATURE - #
161
Loss of Air Flow
*ALARM* - AIR FLOW - #
Fire Supervisory
2AA
24 Hour non-Burg
SUPER - FIRE SUPERVISORY - #
2A1
Low Water Pressure
SUPER - LOW WATER PRESSURE - #
2A2
Low CO2
SUPER - LOW CO2