A minimal amount of static is generated. Ensure that the outlet of the trap is lower than the inlet and the
bottom of the trap is at least 2” lower than the outlet. Waterless traps are an acceptable substitute.
Figure 26 – Gas Heat Sectional View of Condensate Trap Requirements
Traps are installed to keep an air gap in-between the flue gases, condensate generated during combustion,
and the building drain. Improper installation or application of the traps can lead to poor combustion
(excessive amounts of CO) and/or cause the heating unit to not operate.
Where condensate drains are located outside of a heated space and temperatures will fall below freezing,
the entire drain line and trap must be thermally protected. Use a 2.5 to 5 watt per foot at 115VAC, 40°F
self-regulating, shielded and waterproof heat tape. A receptacle has been provided in the heating vestibule
for this purpose.
Condensate drain lines must always be sloped toward the discharge for proper condensate removal. For
installation where the building drain lines are above the level of the duct furnace drain system, a condensate
pump may be required. Note that the products of combustion can be highly corrosive. Ensure that the
condensate pump is rated for gas heat flue condensation.
2.10.9 Induced Draft Fan
An induced draft fan or combustion air blower are products which incorporate an integral fan or blower as
part of the heater assembly to provide metered air for the combustion process.
Even with these fans in place, certain applications such as horizontal side wall venting are limited in the
length of vent piping that can be applied due to pressure drop in the vent. HDA series furnaces are limited to
a maximum vent length of 50 lineal feet of 6” diameter pipe. Depending on the pipe diameter, fittings need
to be included in determining the total lineal feet. Depending on heater location, routing of the vent pipe and
other requirements, vent piping may exceed the maximum vent length listed for the product.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...