Follow these instructions for installation of the radiation shield:
1. Loosen plastic probe retainer on radiation shield by unscrewing two retainer screws.
2. Remove the plastic probe retainer and substitute with the two-sided plastic probe retainer
that is included with the unit.
3. Slide humidity transmitter probe completely into radiation shield.
4. Screw plastic probe retainer to the radiation shield until the probe is firmly held in place.
Do not over tighten the screws.
5. Integral pipe mounting hardware should be removed for surface mounting applications.
To do this, remove the u-bolt and screw holding the pipe retaining bracket.
6. Mark the outer two holes of the mounting bracket on the flat surface.
7. Drill these two holes marked in the previous step.
8. Attach the radiation shield to the flat surface.
9. Wire the sensor harness to the junction box wires per the below color chart. For your
convenience, the sensor wires are pre-installed to the SP control panel and terminate in a
junction box with quick connect wire lever locks.
The wiring color coding is as follows:
Junction Box
White
Green
Red
Black
Sensor Harness
White
Blue
Brown
Black
10. Attach the wire harness as shown in Figure 16 below to the T/RH 309 Sensor.The sensor
has a female end and the male wire harness threads onto the T/RH 309 Sensor
.
Figure 16 – T/RH Sensor and Wire Connector
2.8.2 Water Temperature Sensor
Desert Aire dehumidifiers ordered with the pool water heating option are supplied with a water
temperature sensor and an aqua stat well.
• Screw the well into the adapter fitted into the pool water piping. The well is equipped with a
1/2” MPT connection.
• Install the sensor upstream from the dehumidifier such that the inlet water temperature is
sensed. The auxiliary pool water heater should not be installed upstream of the dehumidifier.
Install heater downstream or in parallel with the dehumidifier.
• The sensor must be installed in a location where it will accurately sense the pool water
temperature. This means you must have continuous water flow at the sensor location.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...