19
Desert Aire - SP Manual
2.2 Outdoor Air and Exhaust Air
Desert Aire SelectAire Plus™ dehumidifiers are equipped with an opening which will draw outdoor air
into the conditioned space. This will help you comply with ASHRAE Standard 62, which requires the
introduction of outdoor air into commercial buildings.
Additionally, the SelectAire Plus™ unit is equipped with fans and dampers for exhausting air from the
building. This ensures that the building is at a negative static pressure relative to adjacent spaces and
outdoors.
Several modes may be available that provide for different outside air and exhaust flow rates. These
modes are Unoccupied mode, Occupied mode, Event mode, Purge mode and Max OA mode.
See Section 5.5.1 for more details. The ducting method you use depends on the SelectAire Plus™
type of dehumidifier you purchased.
2.2.1 Units with Outdoor Air Only
A SelectAire Plus™ unit configured for indoor installation has a module which contains filters
and a factory-installed damper and actuator. The outdoor air is distributed between the
evaporator and the reheat condenser coils. The unit controller will energize dry contacts to
control any additional outdoor air dampers. This controller will also control the internal exhaust
fans. Figure 6 shows typical ducting for the SelectAire Plus™ unit configured for indoor
installation. The outdoor air duct used for indoor units must be insulated to prevent condensation
from forming on it during the winter. Since cold outdoor air can cause moisture to condensate
and freeze on surfaces when it mixes with the warm, humid return airstream, you must
preheat the outdoor air whenever possible.
When equipped for indoor installation the SelectAire Plus™ unit will also have a connection
exhaust air duct. The humid exhaust air may form an icy fog when it blasts outside during the
winter. Install the outlet grille in a location where this fog will not damage the building or create
a safety hazard. The SelectAire Plus™ has several options for location of the exhaust air
discharge. See submittal documentation and general arrangements for locations of connections
for a particular unit.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...