1. Route the tubing such that it will not be subject to damage.
2. Do not directly attach the tube to surfaces that may become very cold such as
suction lines or supply ducts as condensation may occur in the tubing.
3. It is recommended that all of the tubing length be used as this helps buffer any
fluctuation in the sensor readings due to wind gusts.
4. Excess tubing should be coiled at some convenient location rather than cut.
5. Connect the tubing to the static pressure differential transducer in the unit.
6. The correct port is labeled for the outdoor air sensor.
7. Closely observe that the indoor static pressure sensor and outdoor static
pressure sensor are installed on the proper ports as labeled.
2.8.4 Installation of VOC Monitoring Sensor
Desert Aire provides a Volatile Organic Compound (VOC) monitoring sensor that can trigger a
greater flow rate of outdoor air when indoor contaminants reach a user determined
concentration. A sensor will be provided in the unit or shipped loose for field installation
depending on the configuration ordered.
VOC Sensor in the Unit
If ordered with Sensor in Unit the sensor is included downstream of the filter rack. The level of
the VOC in parts per million will immediately be available when the controller is powered on. It
should be noted that for reasonable accuracy that the fan should be constantly powered.
VOC Sensor in Zone
If ordered with Sensor in Zone the sensor is shipped loose for field mounting. This sensor should
be mounted in a space that represents the typical breathing zone for the occupants or directly in
the unit. The back mounting plate is suitable for mounting on a 2” x 4” J-Box or directly to drywall.
Screws are provided.
Three wires are required and terminals on the sensor can accommodate 16 to 22 AWG. 18 AWG
wire can be used up to 500 ft. run. Terminate wires as shown on the low voltage diagram.
Check to ensure that the sensor output has been set for 0-5 VDC output. The J3 jumper should
be set in the storage position. See data sheet supplied with sensor for additional details.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...