96
Testing and Final Diagnosis
Check the oil level in the compressor after the system has been running for 24 hours. Oil
may have been contaminated in the liquid refrigerant when recovered from the system.
Most of this oil will be returned if the recovered refrigerant is used. If new refrigerant is
added, additional oil should be added based on the following ratio:
New Refrigerant Charge Added, lbs. x 0.352 = Oil charge, oz.
It is of critical importance to ensure that the system is operating as expected before the unit
is returned to normal service. Test component replaced and function of the system. Many
times a separate component in the system may have set a condition that causes a failure of
another. Thoroughly test systems to ensure repeat failures do not occur.
5.7 System Rating Plate
The system rating plate is attached near the electrical enclosure of the dehumidifier.
Figure 43 is an example of this rating plate.
R410A ONLY
Model No. SP80XXXXXEXXXXX
Wiring Diagram Numbers:
XXXX-HV1, XXXXX-HV2, XXXXX-LV1, XXXXX-LV2, XXXXX-LV3
Maximum Design
Pressures (psig):
650 High Side
250 Low Side
Figure 43 – SP Dehumidifier Rating Plate
Desert Aire - SP Manual
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...