2.14.2 Packaged Condenser Pre-Filters
Optional Pre-Filters may be included as an option as well. The pre-filters are assembled over the hail
guard netting with the netting being in direct contact with the condenser unit. The coils are not the
same size so take care to assemble the correct pre-filter to the unit.
2.14.2.1
Mounting
The pre-filters share the same clips as the hail guard. See Section 2.14.1 for a
description of removal and re-assembly of the pre-filters to the unit.
2.14.2.2
Inspection
Pre-filters are intended to become part of your normal maintenance program. Visual
inspection for debris build up on the pre-filters should be completed at a minimum of
every 4 months or sooner depending on the application, the environment and the
use of the equipment.
2.14.2.3
Cleaning
Pre-filters may be cleaned in a variety of ways, including:
- Brushing / broom cleaning (in place on equipment or removed)
- Vacuuming (in place on equipment or removed)
- Hose cleaning with or without detergents and rinsed thoroughly by hosing
from the reverse side (removed).
2.15 Section Cabinet Assembly Instructions (Optional)
If the unit has been designed for a sectioned unit installation, please follow the instructions below in addition
to the standard installation instructions included within the unit.
2.15.1 Rigging Instructions
• Refer to the installation instructions included with the unit for lifting procedure.
• In addition, unit sections must be properly braced to ensure safe lifting without damage to the unit.
• The unit is NOT designed to be assembled and lifted as a single unit. Lifting unit as a single piece
may damage the cabinet, internal machinery, and endanger personnel.
2.15.2 Cabinet Assembly
• Align sections on a flat surface to facilitate unit assembly. For units with three or more sections
number identifiers have been placed on the unit splits to ensure proper mating of sections
(refer to Figure 29). Place common numbers next to one another.
• Units with refrigeration circuit splits have varying amounts of refrigeration reconnections required
depending on the unit size and configurations. Inspect the unit and identify all refrigeration breaks.
There will be a service valve on either side of the joint to be connected.
• Clean pipe stubs to be connected then mark 1/2 of coupling depth on each pipe stub for reference
during assembly. Slide coupling on one side of the connection to be made prior to section
alignment and connection.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...