85
5.3
Pool Water Chemistry
Pool chemistry must be maintained to ensure the proper pH, total alkalinity, calcium hardness, and
free chlorine, NSPI recommends the following levels for pool chemistry:
• pH:
7.4 – 7.6
• Total Alkalinity:
100 – 150 ppm
• Calcium Hardness:
200 – 250 ppm (Plaster Pool)
• Free Chlorine:
1.0 – 3.0 ppm
Excessive chemical levels in the pool can be dangerous to users and can damage pool hardware,
including the dehumidification system. The Desert Aire warranty does not cover equipment damaged
by faulty pool chemistry.
5.4
Recommended Controller Setting
5.4.1 Controller Set Points
It is important to determine your comfortable set points and to avoid further controller
adjustments. It takes time for the unit to establish equilibrium at a given set point.
Therefore, continued set point adjustments will lead to high energy consumption and user
discomfort. Continuous blower operation is recommended. This will reduce air stratification
and assure that the refrigeration circuit is activated only when it is necessary.
RECOMMENDED SET POINTS:
• Humidity: 50% to 60 % RH
• Air Temperature: 2° to 4° F above the pool water temperature
Never disable a dehumidifier in a pool room application unless the pool has been
drained. Even when not in use, pool water continues to evaporate adding moisture
to the air. During these periods of high humidity, moisture will seep into walls,
ceilings, furniture, etc. Although the dehumidifier may be capable of regaining
control of pool room conditions after re-start, in the long run, moisture damage to
the pool room will become apparent.
5.5
System Operating Modes
The standard sequence of operation of a Desert Aire dehumidifier is relatively simple to understand.
Note that the sequence may vary depending on which condenser options have been purchased and
installed.
5.5.1 Basic Sequence
The compressor is designed to start on a call for cooling or dehumidification. As the
refrigerant flows through the evaporators, it absorbs a great deal of heat from the airstream.
This heat can either be rejected to the air, the pool, or to a remote condenser, depending on
Desert Aire - SP Manual
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...