LP Only: Copper and brass tubing and fittings (except tin lined) shall not be used if gas contains more than a
trace (0.3 grains per cubic ft.) of hydrogen sulfide gas. Check with your gas supplier.
LP Only: Maximum supply pressure for liquefied petroleum (LP) gas is 13.5” w.c. and minimum supply for
purpose of input adjustment is 11” w.c.
Before attempting to measure or adjust high fire manifold gas pressure, the inlet (supply) pressure must be
within the specified range for the gas being both used when the heater is in operation and on standby.
Incorrect inlet pressure could cause excessive manifold gas pressure immediately or at some future time.
With the manual valve, on the combination valve, positioned to prevent flow to the main burners, connect
a manometer to the 1/8” pipe outlet pressure tap on the valve. Open the valve and operate the heater to
measure the manifold gas pressure.
Note:
A manometer (fluid filled gauge) is recommended rather than a spring type gauge due to the difficulty of
maintaining calibration of a spring type gauge. Normally adjustments should not be necessary to the factory
preset regulator. If adjustment is necessary, set pressures to above settings by turning regulator screw in
(clockwise) to increase pressure. Turn regulator screw out (counter clockwise) to decrease pressure. Consult
the valve manufacturer’s literature provided with the heater for more detailed information.
2.10.3 Gas Heater Location
The following items must be considered when choosing the size and location of the furnace. Note that
dehumidifiers designed for outdoor use are already equipped with combustion air intakes and venting means.
Field-installed venting is only required on indoor dehumidifiers.
All local codes and/or regulations take precedence over the instructions in this manual and should be
followed accordingly. In the absence of local codes, installation must conform to these instructions,
regulations of the National Fire Protection Association, provisions of National Electrical Code (ANSI/NFPA70
latest edition), and the National Fuel Gas Code (ANSI Z223.1 latest edition).
• Indoor units only: The dehumidifier should be located as near the vent terminal as practical to
minimize the numbers of elbows and the length of any horizontal run of connecting flue pipe which
may be required.
• Definitions of “combustible material” and “non-combustible material” as issued by ANSI Z223.1 are
as follows:
- Combustible Material: Material made of or surfaced with wood, compressed paper, plant
fibers, plastics or other material that will ignite and burn whether flameproof or not or
whether plastered or not.
- Non-Combustible Material: Material which will not ignite and burn; such materials
consisting entirely of steel, iron, brick, concrete, slate, glass, plaster, or combination
thereof.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...