3.4 General Testing
After you balance the airflow and test the refrigeration circuits, verify that the other equipment and
accessories connected to the dehumidifier work properly. Although this may be difficult, since the dehumidifier
is usually interlocked with a variety of equipment installed by different contractors, you must not skip this step.
Each of these devices (which may include auxiliary air and water heaters, smoke alarms, circulating pumps
and a building management system) is vital in maintaining the performance and comfort of the swimming pool
environment. Many customer complaints are caused by improper interlocks between these devices. Make
sure you check the following:
• Check the outdoor air and exhaust devices. The outdoor air and exhaust dampers must open when
they receive an “occupied” signal from the dehumidifier. If you have installed an exhaust blower,
make sure that it is interlocked with the “occupied” signal or with an end switch on the outdoor air
damper actuator.
• Check the condensate drain to make sure it has been trapped and primed with water. Verify that it
drains freely, with no leaks. If the drain is outside or in an unconditioned space, make sure it has
been heat traced. If you installed a condensate pump, make sure it operates properly.
• Check the pool water piping to the dehumidifier (on units equipped with optional pool water
heating). Make sure that all air has been bled out of the lines, and check that an air bleed valve
has been installed at any high points in the water lines. If the circulating pump is not set for
continuous operation, make sure it properly interlocked with the dehumidifier. Temporarily shut off
the water flow to the unit to verify that the factory-installed water flow proving switch operates
correctly. Verify that the pool water temperature sensor has been installed where water will flow
over it continuously. Verify that the pool water temperature sensor is on the water inlet of the unit.
• Check the operation of the remote condenser (on units equipped with this option). Make sure that
the pressure transducers are wired to the condenser fan cycling control, the cut-in and cut-out
pressures are correctly set per the remote condenser installation manual. Verify that the fans are
blowing vertically upward when they run.
• Check the temperature and humidity readings displayed on the controller. If you think the values
are incorrect, check the sensor or its field-installed wiring for damage. If necessary, check the
voltage jumper on the temperature and humidity sensor. It must be set in the “0-10 VDC” position.
3.5 Routine Maintenance Schedule
3.5.1 Service Every Month
• Check and replace the air filters in the return duct and the outdoor air duct.
• Check for dirty coils in the dehumidifier. Clean them if necessary.
3.5.2 Service Every Four Months
3.5.2.1 Reheat Condenser Coil Cleaning
Refrigerant coils or other components that corrode due to improper cleaning, improperly
balanced pool chemistry or corrosive air quality will not be covered under the warranty.
Maintenance
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...