In these cases, a vent booster fan (also referred to as a power venter) may be applied to the vent system to
overcome the additional pressure loss and insure products of combustion are properly exhausted.
Precision Vent, and other vent system manufacturers, provide venting solutions for indoor gas heater
installations. These systems typically include a booster fan (power venter).
Precision Vent can be contacted at:
829 Pickens Industrial Drive, Suite 5
Marietta, GA 30062
Tel: 678-213-1332
2.11 Auxiliary Pool Water Heating
A properly sized Desert Aire dehumidifier equipped with the pool water heating option can maintain the pool
water temperature under normal conditions. However, like any refrigerated dehumidifier, the Desert Aire unit
may require days to heat a recently-filled pool by itself. For this reason, you should install an auxiliary pool
heater.
Desert Aire dehumidifiers ordered with the water heating option are provided with a set of dry contacts for
controlling an auxiliary pool water heater. The dehumidifier will be the primary source of water heating. If it
cannot keep up with the demand for pool heat, the Desert Aire controller will then energize the auxiliary water
heater.
Note:
Do not use the aqua stat mounted on the auxiliary heater for temperature control. This can lead to
excessive water temperature fluctuation. It may also permanently prevent the dehumidifier from heating pool
water if the set point of the heater aqua stat is higher than the water heating set point of the dehumidifier.
2.12 Smoke Alarm Interlock
Desert Aire SP series dehumidifiers are equipped with a set of terminal blocks for interlocking with the smoke
alarm (alarm provided and installed by others). The smoke alarm contacts must be rated for at least 15 amps
at 24 VAC. The contacts must break when smoke is present. This will shut off the blower(s) and compressors.
See the dehumidifier wiring diagram for connection details.
2.13 Auxiliary Air Heater – Hot Water Coils
Initial Fluid Start-Up Prep
• Open all vents so that air is eliminated from within the coil circuitry and headers. Verify that all
vents and drains are not obstructed and do discharge a stream of water.
• Fill the coil with water (or glycol mix) then close all vents.
• Perform an initial hydrostatic leak test of all brazed, threaded or flanged joints, valves and
interconnecting piping. Recheck the coil level and correct if necessary. When the setup is found
to be leak free, discharge and discard initial water charge. It is important that all grease, oil, flux
and sealing compounds present from the installation are removed.
Содержание SelectAire Plus SP Series
Страница 2: ...2 ...
Страница 12: ...12 Desert Aire SP Manual ...
Страница 76: ...76 Figure 41 Filter Drier Assembly Desert Aire SP Manual ...
Страница 101: ...101 Desert Aire SP Manual ...
Страница 102: ...102 Desert Aire SP Manual ...
Страница 103: ...103 Desert Aire SP Manual ...
Страница 104: ...104 Desert Aire SP Manual ...
Страница 105: ...105 Desert Aire SP Manual ...
Страница 106: ...106 Desert Aire SP Manual ...
Страница 109: ...109 Desert Aire SP Manual ...