07 Descriptions of Parameter Settings | REG2000
7-13
Number of times of auto-restart after fault
Default:
0
Settings 0–10
Sets the number of times the Power Regenerative Unit can automatically reset/restart after a fault
(acceptable errors: only over-current during regeneration and at stop, over-voltage during
regeneration and at stop, phase lock) at a maximum of ten times. If you set this parameter to 0, then
the system does not automatically reset/restart after a fault.
Auto-restart interval of fault
Default:
60.0
Settings 0.1–6000.0
sec.
When a restart after fault occurs, the Power Regenerative Unit starts a count-down according to this
parameter. Within the Pr.03-08 setting time, the Power Regenerative Unit stops only when the
count-down reaches the number of times set in Pr.03-07 (and the faults are recorded). If the
count-down does not reach the number of times set in Pr.03-07 within Pr.03-08 setting time, the unit
resets Pr.03-07 to the initial value before starting another counting.
Cooling fan control mode
Default:
3
Settings 0: fan runs always
1: runs for one minute after stop and then stops
2: runs and stops as the Power Regenerative Unit regenerates and stops
3: runs according to the power module’s temperature
4: always off
Determines the cooling fan mode setting.
0: The cooling fan starts running as soon as the Power Regenerative Unit starts transmitting power.
1: The cooling fan runs when the Power Regenerative Unit runs and stops one minute after the
Power Regenerative Unit stops.
2: The cooling fan runs when the Power Regenerative Unit runs and stops as soon as the Power
Regenerative Unit stops.
3: The cooling fan adjusts its speed according to the power module’s temperature. When the
temperature is high, the cooling fan starts running; the higher the temperature the faster the fan runs.
When temperature drops into the normal range, as shown in the following table, the cooling fan
stops.
4: The cooling fan is always off.
Model
Operating temperature range of fans (RUN
STOP)
REG075A23A 50
40
REG110A23A 60
50
REG150A23A 50
40
REG185A23A 50
40
REG220A23A 50
40
REG300A23A 45
35
REG370A23A 65
55
REG075A43A 50
40
REG110A43A 55
45
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...