06 Summary of Parameter Settings | REG2000
6-7
04 Communication Parameters
Parameter
codes
Parameter names
Setting range
Default
04-00
Communication address
1–254
1
04-01
COM1 transmission speed 4.8–115.2
Kbps
9.6
04-02
COM1 transmission fault
treatment
0: Warn and continue operation
1: Warn and ramp to stop
2: Reserved
3: No action and no display
3
04-03
COM1 time-out detection
0.0–100.0 sec.
0
04-04
COM1 communication protocol 0: 7, N, 1 (ASCII)
1: 7, N, 2 (ASCII)
2: 7, E, 1 (ASCII)
3: 7, O, 1 (ASCII)
4: 7, E, 2 (ASCII)
5: 7, O, 2 (ASCII)
6: 8, N, 1 (ASCII)
7: 8, N, 2 (ASCII)
8: 8, E, 1 (ASCII)
9: 8, O, 1 (ASCII)
10: 8, E, 2 (ASCII)
11: 8, O, 2 (ASCII)
12: 8, N, 1 (RTU)
13: 8, N, 2 (RTU)
14: 8, E, 1 (RTU)
15: 8, O, 1 (RTU)
16: 8, E, 2 (RTU)
17: 8, O, 2 (RTU)
1
04-05
Communication response
delay time
0.0–200.0 ms
2.0
04-06 Reserved