08 Warnings and Error Codes | REG2000
8-8
message still appears, contact a local dealer near you or Delta to return the
product.
57
CE4
PC slave fault
Fault
Data written to read-only addresses
Corrective Action
Verify that the communication wring is correct.
Check that the communication address is correct.
Press the RESET button after verifying the above items. If the error
message still appears, contact a local dealer near you or Delta to return the
product.
58
CE10
PC time out
Fault
Modbus transmission time-out
Corrective Action
Verify that the communication wring is correct.
Press the RESET button after verifying the above item. If the error
message still appears, contact a local dealer near you or Delta to return the
product.
66
PLE
Phase Lock Err
Fault
While regenerating, the mains electricity frequency is not between 47–63
Hz (see Mains Frequency Range in Chapter 03 Specification) and the
deviation time is longer than the setting in Pr.03-04.
Corrective Action
Verify that the mains frequency is normal.
Verify that the mains three-phase wiring is correct.
Press the RESET button after verifying the above items. If the error
message still appears, contact a local dealer near you or Delta to return the
product.
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...