tH2o
Thermo 2 open
Fault
The Power Regenerative Unit detects a temperature lower than normal
(lower than -30ºC) at the power module or a circuit error in temperature.
Corrective Action
Increase the temperature and press the RESET button after verifying the
above items. If the error message still appears, contact a local dealer near
you or Delta to return this product.
21
oL
Over load
Fault
Output current (AC) exceeds the Power Regenerative Unit allowed rated
current. (See REG2000 Performance Curve in Chapter 03 for the duration
(seconds) of output current in the allowable range.)
Corrective Action
Verify that you chose the right Power Regenerative Unit. See Chapter
10 Power Regenerative Unit Selection for more information.
Press the RESET button after verifying the above items. If the error
message still appears, contact a local dealer near you or Delta to return this
product.
30
cF1
EEPROM write Err
Fault
Memory write error
Corrective Action
Press the RESET button to restore the system to the default setting. If the
error message still appears, contact a local dealer near you or Delta to
return this product.
31
cF2
EEPROM read Err
Fault
Memory read error
Corrective Action
Press the RESET button to restore the system to the default setting. If the
error message still appears, contact a local dealer near you or Delta to
return this product.
37
Hd1
oc HW error
Fault
OC protection hardware circuit error
Corrective Action
Current detection error at first power-on. This error cannot be reset.
Shut down the system and then turn the power back on. If the error
message still appears, contact a local dealer near you or Delta to return this
product.
38
Hd2
Ov HW error
Fault
OV protection hardware circuit error
Corrective Action
Voltage detection error at first power-on. This error cannot be reset.
Shut down the system and then turn the power back on. If the error
message still appears, contact a local dealer near you or Delta to return this
product.
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...