07 Descriptions of Parameter Settings | REG2000
7-11
6 Warn
indicator
The contacts are ON when the Power Regenerative Unit
detects a warning.
7
No function
The output terminal does not have any function
See Diagram 3 in Section 4-4 for more information on the definition of different working status of
power regeneration.
Multi-function output direction
Default:
0
Settings 0–65535
The setting of this function is binary. If you set a bit to 1, the multi-function output direction is
reversed. For example, when you set Pr.02-07 to 1 (Regenerate indicator), if the output direction is
forward or you set the bit to 0, Relay 1 activates (ON) only when the Power Regenerative Unit
regenerates. When the Power Regenerative Unit is stopped, Relay 1 is OFF. In contrast, if the
output direction is reverse and you set the bit to 1, Relay 1 is OFF when the Power Regenerative
Unit regenerates, and ON when it stops.
Bit 2
Bit 1
Bit 0
MO2 MO1 RY1
Relay 1
MO1
1 0
2
MO2
2
1
0
2
2
2
Weights
Bit
0=ON
1=OFF
Note
2 =4 2 =2 2 =1
2
1
0