07 Descriptions of Parameter Settings | REG2000
12
03 Special Protection Parameters
You can set this parameter during operation.
Low voltage level
Default:
180.0/360.0
Settings 230V series: 160.0–220.0 V
460V series: 320.0–440.0 V
This parameter sets the LV voltage level.
When the Power Regenerative Unit voltage drops below the parameter low voltage level, the
system sends a warning.
LV
03-00
Input voltage
30V(60V)
Current limit
Default:
150
Settings 0–150%
Limits the Power Regenerative Unit maximum current output.
Reserved
Reserved
Phase lock frequency deviation time
Default:
150
Settings 0–1000
ms
When a frequency is detected to be outside of 47–63 Hz and the duration is longer than the value
set in this parameter, the system generates a PLE phase lock signal.
External power supply card 24 V (EMC-BPS01) enabled
Default: 0
Settings
0: EMC-BPS01 disabled
1: EMC-BPS01 enabled
When using EMC-BPS01 as the external power supply for the Power Regenerative Unit,
enable EMC-BPS01 through communications or digital keypad to prevent RyF error. (Only
REG2000 manufactured after March 2018 supports this function.)
Reserved