04 Wiring | REG2000
4-19
Terminal
Function Description
Default (NPN mode)
MO2
Multi-function output 2 (photo
coupler)
MO2
MCM
MO1
MCM
Common terminal for
multi-function outputs
Max 48 V
DC
50 mA
RA1
Multi-function relay output 1
(N.O.) a
Resistive load
5 A (N.O.)/3 A (N.C.) 250 V
AC
5 A (N.O.)/3 A (N.C.) 30 V
DC
N.O. minimum load: 5 V/0.1 A; 24 V/ 3 mA
N.C. minimum load: 5 V/ 0.1 A; 24 V/ 3 mA
Inductive load (COS 0.4)
2.0 A (N.O.)/1.2 A (N.C.) 250 V
AC
2.0 A (N.O.)/1.2 A (N.C.) 30 V
DC
Outputs various monitoring signals.
N.O. minimum load: 5 V/ 0.1 A; 24 V/3 mA
N.C. minimum load: 5 V/ 0.1 A; 24 V/3 mA
RB1
Multi-function relay output 1
(N.C.) b
RC1
Common terminal for
multi-function relays
SG+ Modbus
RS-485
PIN 1, 2, 7, 8: Reserved PIN 3, 6: GND
PIN 4: SG- PIN 5: SG+
SG-
NOTE: Analog control signals wire size: 18 AWG (0.75 mm
2
) with shielded wire
Contact Input Terminals (MI1–MI5, COM)
When using contacts or switches to control the input terminals, use high quality components to
prevent contact bounce.
Transistor Output Terminals (MO1, MO2, MCM)
Make sure to connect the digital outputs to the correct polarity.
When connecting a relay to the digital outputs, connect a surge absorber across the coil and
check the polarity.
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...