08 Warnings and Error Codes | REG2000
8-7
42
5VF
5V fault Err
Fault
Power supply (5V) on control board error
Corrective Action
Shut down the system and then turn the power back on. Wait for at least
five seconds, make sure the supply power is normal, and then reset this
error. If the error message still appears, contact a local dealer near you or
Delta to return this product.
43
RYF
Relay fault Err
Fault
Relay error
Corrective Action
Press the RESET button to return the system to the default setting. If the
error message still appears, contact a local dealer near you or Delta to
return the product.
49
EF
External fault
Fault
External command causes external fault (EF) and closes terminal (MOx).
The Power Regenerative Unit stops output.
Corrective Action
Press the RESET button after clearing the faults. If the error message still
appears, contact a local dealer near you or Delta to return the product.
52
Pco
Password error
Fault
Password entered incorrectly for three consecutive times
Corrective Action
See Pr.01-02 and Pr.01-03.
Shut down the system and then turn the power back on to enter the
correct password.
54
CE1
PC Err command
Fault
Illegal communication command
Corrective Action
Verify that the communication wring is correct.
Check if communication commands are correct (communication
commands must be 03, 06, 10, 63).
Press the RESET button after verifying the above items. If the error
message still appears, contact a local dealer near you or Delta to return the
product.
55
CE2
PC Err address
Fault
Illegal communication address (00H–254H)
Corrective Action
Verify that the communication wring is correct.
Check if the address of communication data is correct.
Press the RESET button after verifying the above items. If the error
message still appears, contact a local dealer near you or Delta to return the
product.
56
CE3
PC Err data
Fault
Illegal communication data value
Corrective Action
Verify that the communication wring is correct.
Check if the communication data value exceeds the maximum /
minimum values (see Chapter 07).
Press the RESET button after verifying the above items. If the error
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...