04 Wiring | REG2000
4-21
Power & Alarm Indicator Status Descriptions
ALARM
POWER
Description
Note
Blinking red + green
lights
Blinking red + green
lights
Prepare*
Once the Power
Regenerative Unit is
powered on, it performs
auto-system checking.
OFF
Constant red light ON
Ready**
Once the Power
Regenerative Unit is
powered on, if there are no
faults or warnings and
phase lock is completed,
you can now send the RUN
command.
OFF
Constant green light ON RUN**
Once you send the RUN
command, the Power
Regenerative Unit runs
smoothly and waits for the
conditions to regenerate
energy.
OFF
Blinking green light
REGENERATE**
Power Regenerative Unit
regenerates AC current to
the mains power.
ALARM
POWER
Description
Fault/Warning Name
Corresponds to the Keypad
Constant red light ON
Blinking red light
OV (Over-voltage) ovn, ovs
Constant red light ON
Blinking green light
EF (External fault) EF
Constant red light ON
Constant red light ON
OL (Overload)
oL
Blinking red light
Constant red light ON
OH (Overheat)
oH1, oH2, tH1o, tH2o
Constant red light ON
OFF
OC (Over-current) ocn, ocs
Blinking red light
Blinking red light
Comm. Err.
(Communication
fault)
Pco, CE1, CE2, CE3, CE4,
CE10, SE1, SE2, SE3
Blinking red light
OFF
Mains Err.
(Mains power
error)
Phase loss (OrP), phase
lock (PLE) and low direct
voltage (LvS) warning at
input.
Blinking green light
Blinking green light
HW Err.
(Hardware fault/
memory fault)
cd1, cd2, cd3, Hd1, Hd2,
5VF, RYF, cF1, cF2
*The start-up time is too short, so there is no message on the keypad.
**Different regeneration statuses are defined in Diagram 3 below.
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...
Страница 68: ...05 Optional Accessories REG2000 5 22 Removing the EMC BPS01...