06 Summary of Parameter Settings | REG2000
6-3
Parameter
codes
Parameter names
Setting range
Default
00-21
Fault record 2
3: ocn over-current during regeneration
0
00-22
Fault record 3
6: ocs over-current at stop
0
00-23
Fault record 4
9: ovn over-voltage during regeneration
0
00-24
Fault record 5
10: ovs over-voltage at stop
0
00-25
Fault record 6
15: OrP phase loss in output
0
16: oH1 power module overheated
17: oH2 internal ambient temperature overheated
(air outlet)
18:
tHo1 power module overheated protection
circuit error
19:
tHo2 internal ambient temperature overheated
protection circuit error
21: oL overload
30: cF1 memory writing error
31: cF2 memory read error
37: Hd1 current detection error when powering on
38: Hd2 voltage detection error when powering on
42: 5VF 5 V control board error (firmware v.1.02
(included) and later)
43: RYF relay error (firmware v.1.02 (included) and
later)
49: EF external signal input fault
52: Pcod wrong password
54: cE1 communication error
55: cE2 communication error
56: cE3 communication error
57: cE4 communication error
58: cE10 communication time-out
66: PLE phase lock error
00-26
Low word in electricity bill
Read Only
00-27
High word in electricity bill
Read Only
00-28
Display input AC voltage
(V
AC
)
Read Only
Содержание REG2000 Series
Страница 44: ...04 Wiring REG2000 4 20 4 4 Display Panel Indicators Display Panel...
Страница 51: ...05 Optional Accessories REG2000 5 5 How to remove the plastic cap 1 Press the pin on top of the keypad...
Страница 67: ...05 Optional Accessories REG2000 5 21 5 5 External Power Supply Card 24 V EMC BPS01 Installing the EMC BPS01...