06 Summary of Parameter Settings | REG2000
6-6
03 Special Protection Parameters
Parameter
codes
Parameter names
Setting range
Default
03-00
Low voltage level
230V series:160.0–220.0 V
460V series:320.0–440.0 V
180.0
360.0
03-01
Current limit
0–150%
150
03-02
Reserved
03-03
Reserved
03-04
Phase lock frequency
deviation time
0–1000 ms
150
03-05
External power supply card
24 V (EMC-BPS01) enabled
0: EMC-BPS01 disabled
1: EMC-BPS01 enabled
0
03-06
Reserved
03-07
Number of times of
auto-restart after fault
0–10 0
03-08
Auto-restart interval of fault
0.1–6000.0 sec.
60.0
03-09
Cooling fan control mode
0: fan runs always
1: runs for one minute after stop and then stops
2: runs and stops as the Power Regenerative Unit
regenerates and stops
3: runs according to the power module’s
temperature
4: always off
3
03-10 Reserved
03-11 Reserved
03-12
Erase the energy regenerated
record
0: parameter reset
1: erase
0
03-13
Electricity rate
0–6553.5 $ / kWh
3.0