Appendix A. Single-phase Application
| IED-S
A-2
A.2 Key Points to Consider when Using the Three-phase Drive for Single-
phase Power Input
DELTA IED-S drives have been tested and UL certified for the application of single-phase power input
under proper reduced rated capacity. To ensure operational safety and service life, pay attention to the
precautions in this document to connect the motor and load correctly.
When using the three-phase drive with single-phase power input, ensure the power input is from the
R-S (L1-L2) terminal. Due to the increase in DC bus ripple voltage and current, it is necessary to reduce
the rated output current and horsepower of the drive. In addition, approximately doubled current is
generated at the diode rectifier bridge when input current passes through the second phase, so reducing
ratings in drives becomes a consideration. The reasons for the increase in single-phase input current lie
in the conversion of three-phase current to single-phase current (
√
3) and the decrease in overall power
factor. Because of the increase in harmonic distortion of input current, the overall input power factor is
lower than that in three-phase input current. If the overall power factor is 0.7, a typical value for single-
phase power input, it is recommended to install a reactor. If the power factor is 0.9, also a typical value for
three-phase power input, it is also recommended to install a reactor. Note that if you use single-phase
power input without installing reactors, 100% input current distortion may occur.
When using single-phase input power for IED-S, set output rated current as follows:
1. Reduce output rated current to 50% if no AC reactors are installed
2. Reduce output rated current to 55% if 3% AC reactor is installed
3. Reduce output rated current to 60% if 5% AC reactor is installed
Table A.2-1:
Applicable drives for IED-S with motors
Table A.2-2: Applicable drives for IED-S with motors when 3% AC reactor is installed at drive power input
Table A.2-3: Applicable drives for IED-S with motors when 5% AC reactor is installed at drive power input
IED-S 230V
Motor (kW)
Input Phase
Drive’s Input
Rated Current
Drive’s Output
Rated Current
Applicable Drives (kW)
Line Fuse
2.2 R-S
(L1-L2) 26.4 12 5.5
JJN-50
3.7 R-S
(L1-L2) 37.4 17 7.5
JJN-80
Table A.2-1
3% AC Reactor is Installed for IED-S 230V
Motor
(kW)
Input Phase
Drive’s
Input
Rated
Current
Drive’s
Output
Rated
Current
Applicable
Drives (kW)
3%
Reactors
(mH)
Reactor
Saturation
Current
(Arms)
Reactors
(Delta P/N)
Line Fuse
2.2 R-S
(L1-L2) 20.9
12
5.5 0.441 43.2 N/A JJN-50
3.7 R-S
(L1-L2) 32.3
17
7.5
0.32 55.8
DR033AP320
JJN-80
Table A.2-2
5% AC Reactor is Installed for IED-S 230V
Motor
(kW)
Input Phase
Drive’s
Input Rated
Current
Drive’s
Output Rated
Current
Applicable
Drives (kW)
3% Reactors
(mH)
Reactor Saturation
Current (Arms)
Line Fuse
2.2 R-S
(L1-L2) 20.9
12
5.5 0.735
43.2 JJN-50
3.7 R-S
(L1-L2) 32.3
17
7.5 0.534
55.8 JJN-80
Table A.2-3
Содержание IED-S Series
Страница 3: ......
Страница 10: ...Chapter 1 Introduction IED S 1 3 1 2 Model Name 1 3 Serial Number...
Страница 24: ...Chapter 2 Installation IED S 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 25: ...Chapter 2 Installation IED S 2 6 The page intentionally left blank...
Страница 29: ...Chapter 3 Wiring IED S 3 4 IED S Integrated Elevator Drive System Wiring Diagram 01 System Configuration...
Страница 32: ...Chapter 3 Wiring IED S 3 7...
Страница 35: ...Chapter 3 Wiring IED S 3 10 3 3 Related Wiring Diagrams 03 Main Circuit for Drive Control Synchronous...
Страница 36: ...Chapter 3 Wiring IED S 3 11 04 Main Circuit for Drive Control Asynchronous...
Страница 38: ...Chapter 3 Wiring IED S 3 13 06 Safety Hatch...
Страница 39: ...Chapter 3 Wiring IED S 3 14 07 Brake Circuit...
Страница 40: ...Chapter 3 Wiring IED S 3 15 08 Inspection Circuit Cartop Inspection Connected to IED S Control Board...
Страница 42: ...Chapter 3 Wiring IED S 3 17 10 Input Contacts of Main Control Board for the Control Panel...
Страница 43: ...Chapter 3 Wiring IED S 3 18 11 Output Contacts of Main Control Board for the Control Panel...
Страница 44: ...Chapter 3 Wiring IED S 3 19 12 Contacts of Cartop Board OCB...
Страница 45: ...Chapter 3 Wiring IED S 3 20 13 Maneuvering Box 1 16 Floor ICB...
Страница 46: ...Chapter 3 Wiring IED S 3 21 14 1 Hall Call System...
Страница 50: ...Chapter 3 Wiring IED S 3 25 15 Lighting Circuit...
Страница 51: ...Chapter 3 Wiring IED S 3 26 16 UCMP Board Three Sensors DZU FL1 and DZD...
Страница 52: ...Chapter 3 Wiring IED S 3 27 17 UCMP Board Four Sensors DZU FL1 FL2 and DZD...
Страница 66: ...Chapter 5 Control Terminals IED S 5 1 Chapter 5 Control Terminals 5 1 Control Terminal Specifications...
Страница 67: ...Chapter 5 Control Terminals IED S 5 2 5 1 Control Terminal Specifications...
Страница 73: ...Chapter 5 Control Terminals IED S 5 8 The page intentionally left blank...
Страница 115: ...Chapter 6 Optional Accessories IED S 6 42 EMC Filter Model No B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 116: ...Chapter 6 Optional Accessories IED S 6 43 EMC Filter Model No B84143D0150R127 Unit mm inch...
Страница 117: ...Chapter 6 Optional Accessories IED S 6 44 EMC Filter Model No B84143D0200R127 Unit mm inch...
Страница 118: ...Chapter 6 Optional Accessories IED S 6 45 EMC Filter Model No B84142A0042R122 Unit mm inch...
Страница 123: ...Chapter 6 Optional Accessories IED S 6 50 The page intentionally left blank...
Страница 143: ...Chapter 7 Option Cards IED S 7 20 The page intentionally left blank...
Страница 151: ...Chapter 9 Digital Keypad IED S 9 4 Keypad Operation Process...
Страница 176: ...Chapter 10 Auto tuning Process IED S 10 9 10 3 2 Default Settings for Output Contacts of IED S Main Control Board...
Страница 177: ...Chapter 10 Auto tuning Process IED S 10 10 10 3 3 Default Settings for Contacts of IED S Cartop Board...
Страница 201: ...Chapter 10 Auto tuning Process IED S 10 34 The page intentionally left blank...
Страница 249: ...Chapter 11 Summary of Parameter Settings IED S 11 48 The page intentionally left blank...
Страница 263: ...Chapter 12 Descriptions of Parameter Settings IED S 12 00 14 The page intentionally left blank...
Страница 273: ...Chapter 12 Descriptions of Parameter Settings IED S 12 01 10 The page intentionally left blank...
Страница 281: ...Chapter 12 Descriptions of Parameter Settings IED S 12 02 8 The page intentionally left blank...
Страница 307: ...Chapter 12 Descriptions of Parameter Settings IED S 12 05 6 The page intentionally left blank...
Страница 319: ...Chapter 12 Descriptions of Parameter Settings IED S 12 06 12 The page intentionally left blank...
Страница 325: ...Chapter 12 Descriptions of Parameter Settings IED S 12 07 6 The page intentionally left blank...
Страница 345: ...Chapter 12 Descriptions of Parameter Settings IED S 12 10 8 The page intentionally left blank...
Страница 349: ...Chapter 12 Descriptions of Parameter Settings IED S 12 11 4 The page intentionally left blank...
Страница 359: ...Chapter 12 Descriptions of Parameter Settings IED S 12 12 10 The page intentionally left blank...
Страница 375: ...Chapter 12 Descriptions of Parameter Settings IED S 12 13 16 The page intentionally left blank...
Страница 381: ...Chapter 13 Warning Codes IED S 13 6 The page intentionally left blank...
Страница 415: ...Appendix A Single phase Application IED S A 4 The page intentionally left blank...
Страница 417: ...Appendix B Revision History IED S B 2 The page intentionally left blank...