Chapter 12 Descriptions of Parameter Settings | IED-S
12-13-2
Settings 0.0–510.0 V
Sets this value according to the motor nameplate. If the motor is 220V, set this parameter to
220.0. If the motor is 200V, set this parameter to 200.0.
Motor Rated Current
Default:
2.00
Settings 0.10–650.00 Amps
Sets this value according to the motor nameplate.
Motor Rated Power
Default:
2.00
Settings 0.10–650.00 kW
Sets this value according to the motor nameplate.
Motor Rated Speed
Default:
0
Settings 0–65535 rpm
Sets this value according to the motor nameplate.
Speed (RPM) = (120 × Frequency) ÷ Number of Motor Poles
Number of Motor Poles
Default:
0
Settings 0–96
Sets this value according to the motor nameplate.
Sets the number of motor poles (must be an even number).
IM No-load Current
Default:
0.00
Settings 0.00–655.35
This value is automatically measured after motor auto-tuning.
IM/PM Rs
IM Rr
Default:
0.000
Settings 0.000–65.535
Ω
The values are automatically measured after motor auto-tuning.
IM Lm
IM Lx/PM Lq
Default:
0.0
Settings 0.0–6553.5 mH
This value is automatically measured after motor auto-tuning.
PM Back Electromotive Force
Default:
0.0
Settings 0.0–6553.5 Vrms
This value is automatically measured after motor auto-tuning.
PM Magnetic Pole Offset Angle
Default:
360.0
Settings 0.0–360.0°
The offset angle between magnetic pole and PG origin (measured by auto-tuning)
Содержание IED-S Series
Страница 3: ......
Страница 10: ...Chapter 1 Introduction IED S 1 3 1 2 Model Name 1 3 Serial Number...
Страница 24: ...Chapter 2 Installation IED S 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 25: ...Chapter 2 Installation IED S 2 6 The page intentionally left blank...
Страница 29: ...Chapter 3 Wiring IED S 3 4 IED S Integrated Elevator Drive System Wiring Diagram 01 System Configuration...
Страница 32: ...Chapter 3 Wiring IED S 3 7...
Страница 35: ...Chapter 3 Wiring IED S 3 10 3 3 Related Wiring Diagrams 03 Main Circuit for Drive Control Synchronous...
Страница 36: ...Chapter 3 Wiring IED S 3 11 04 Main Circuit for Drive Control Asynchronous...
Страница 38: ...Chapter 3 Wiring IED S 3 13 06 Safety Hatch...
Страница 39: ...Chapter 3 Wiring IED S 3 14 07 Brake Circuit...
Страница 40: ...Chapter 3 Wiring IED S 3 15 08 Inspection Circuit Cartop Inspection Connected to IED S Control Board...
Страница 42: ...Chapter 3 Wiring IED S 3 17 10 Input Contacts of Main Control Board for the Control Panel...
Страница 43: ...Chapter 3 Wiring IED S 3 18 11 Output Contacts of Main Control Board for the Control Panel...
Страница 44: ...Chapter 3 Wiring IED S 3 19 12 Contacts of Cartop Board OCB...
Страница 45: ...Chapter 3 Wiring IED S 3 20 13 Maneuvering Box 1 16 Floor ICB...
Страница 46: ...Chapter 3 Wiring IED S 3 21 14 1 Hall Call System...
Страница 50: ...Chapter 3 Wiring IED S 3 25 15 Lighting Circuit...
Страница 51: ...Chapter 3 Wiring IED S 3 26 16 UCMP Board Three Sensors DZU FL1 and DZD...
Страница 52: ...Chapter 3 Wiring IED S 3 27 17 UCMP Board Four Sensors DZU FL1 FL2 and DZD...
Страница 66: ...Chapter 5 Control Terminals IED S 5 1 Chapter 5 Control Terminals 5 1 Control Terminal Specifications...
Страница 67: ...Chapter 5 Control Terminals IED S 5 2 5 1 Control Terminal Specifications...
Страница 73: ...Chapter 5 Control Terminals IED S 5 8 The page intentionally left blank...
Страница 115: ...Chapter 6 Optional Accessories IED S 6 42 EMC Filter Model No B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 116: ...Chapter 6 Optional Accessories IED S 6 43 EMC Filter Model No B84143D0150R127 Unit mm inch...
Страница 117: ...Chapter 6 Optional Accessories IED S 6 44 EMC Filter Model No B84143D0200R127 Unit mm inch...
Страница 118: ...Chapter 6 Optional Accessories IED S 6 45 EMC Filter Model No B84142A0042R122 Unit mm inch...
Страница 123: ...Chapter 6 Optional Accessories IED S 6 50 The page intentionally left blank...
Страница 143: ...Chapter 7 Option Cards IED S 7 20 The page intentionally left blank...
Страница 151: ...Chapter 9 Digital Keypad IED S 9 4 Keypad Operation Process...
Страница 176: ...Chapter 10 Auto tuning Process IED S 10 9 10 3 2 Default Settings for Output Contacts of IED S Main Control Board...
Страница 177: ...Chapter 10 Auto tuning Process IED S 10 10 10 3 3 Default Settings for Contacts of IED S Cartop Board...
Страница 201: ...Chapter 10 Auto tuning Process IED S 10 34 The page intentionally left blank...
Страница 249: ...Chapter 11 Summary of Parameter Settings IED S 11 48 The page intentionally left blank...
Страница 263: ...Chapter 12 Descriptions of Parameter Settings IED S 12 00 14 The page intentionally left blank...
Страница 273: ...Chapter 12 Descriptions of Parameter Settings IED S 12 01 10 The page intentionally left blank...
Страница 281: ...Chapter 12 Descriptions of Parameter Settings IED S 12 02 8 The page intentionally left blank...
Страница 307: ...Chapter 12 Descriptions of Parameter Settings IED S 12 05 6 The page intentionally left blank...
Страница 319: ...Chapter 12 Descriptions of Parameter Settings IED S 12 06 12 The page intentionally left blank...
Страница 325: ...Chapter 12 Descriptions of Parameter Settings IED S 12 07 6 The page intentionally left blank...
Страница 345: ...Chapter 12 Descriptions of Parameter Settings IED S 12 10 8 The page intentionally left blank...
Страница 349: ...Chapter 12 Descriptions of Parameter Settings IED S 12 11 4 The page intentionally left blank...
Страница 359: ...Chapter 12 Descriptions of Parameter Settings IED S 12 12 10 The page intentionally left blank...
Страница 375: ...Chapter 12 Descriptions of Parameter Settings IED S 12 13 16 The page intentionally left blank...
Страница 381: ...Chapter 13 Warning Codes IED S 13 6 The page intentionally left blank...
Страница 415: ...Appendix A Single phase Application IED S A 4 The page intentionally left blank...
Страница 417: ...Appendix B Revision History IED S B 2 The page intentionally left blank...