Chapter 12 Descriptions of Parameter Settings | IED-S
12-03-13
Brake Test Time (Hour)
Default:
2
Settings 0–23
Sets the time (hour) to run the automatic braking force test once per day.
Brake Test Time (Minute)
Default:
59
Settings 0–59
Sets the time (minute) to run the automatic braking force test once per day.
Brake Test Floor
Default:
0
Settings 0–64
Sets the physical floor to run the automatic braking force test once per day. If Pr.03-66=0, the test
runs at the floor where the elevator stops.
Brake Test Starting
Default:
0
Settings 0–1
If Pr.03-67=1, the manual braking force test starts to run. The setting automatically returns to 0
once the test is finished or the test failed.
Manual braking force test
1. Set the time (seconds) to run the braking force test in Pr.03-60 (Brake Test Duration),
ranging from 0.0 to 20.0 seconds.
2. Set the output torque to run the braking force test in Pr.03-61 (Brake Test Output Torque),
ranging from 0% to 200%.
3. Set the car moving distance during braking force test in Pr.03-62 (Brake Test Moving
Distance), ranging from 0.0 to 50.0 mm.
4. Set Pr.03-63 (Brake Test Running Direction). If Pr.03-63=1, the elevator runs upward during
braking force test. If Pr.03-63=0, the elevator runs downward during braking force test.
5. Make the elevator car stop at the leveling position, and the elevator must be in emergency
operation mode or in control panel inspection mode. Moreover, ensure that there is no fault
occurred, and upward operation or downward operation button for the manual mode is not
allowed to press.
6. Set Pr.03-67 (Brake Test Starting) =1 to start the braking force test. If the condition does not
meet the fifth description above, Pr.03-67 immediately returns to 0 after setting to 1, and the
following warning codes occur: 1110 (Inspection, Unqualified, Braking force), or 1111
(Leveling, Unqualified, Braking force), or 1113 (Fault, Unqualified, Braking force), or 1114
(Button, Unqualified, Braking force). However, if the condition meet the fifth description
above, warning codes 1115 (Wait, Braking force test) or 1109 (Braking force, Under test)
occurs.
If the door does not close after setting Pr.03-67=1, the warning code 1115 (Wait, Braking
force test) occurs, and then the door closes automatically. After the door closes, the warning
code 1109 (Braking force, Under test) occurs. Then, the operation contactor outputs
automatically, the brake contactor does not output, torque outputs and gradually increases
to Pr.03-61 (Brake Test Output Torque) setting value.
7. If the car moving distance is not smaller than Pr.03-62 (Brake Test Moving Distance) within
Pr.03-60 (Brake Test Duration) setting time, the test stops automatically and the fault code
F150 (Unqualified braking force test) occurs. At this time, you must press the external reset
device in the manual mode, or press the RESET key on the digital keypad in the manual
mode, or press and hold both the upward operation and downward operation buttons
simultaneously in the manual mode for more than five seconds to reset the fault code F150.
If the car moving distance is smaller than Pr.03-62 (Brake Test Moving Distance), and time
exceeds Pr.03-60 (Brake Test During), the test also stops automatically and the warning
code 1112 (Braking force, Test, Qualified) occurs.
8. Once the braking force test is finished, Pr.03-67 (Brake Test Starting) automatically returns
to 0. The elevator runs automatically only when the braking force test is qualified. Otherwise,
Содержание IED-S Series
Страница 3: ......
Страница 10: ...Chapter 1 Introduction IED S 1 3 1 2 Model Name 1 3 Serial Number...
Страница 24: ...Chapter 2 Installation IED S 2 5 Ambient Temperature Derating Curve Altitude Derating Curve...
Страница 25: ...Chapter 2 Installation IED S 2 6 The page intentionally left blank...
Страница 29: ...Chapter 3 Wiring IED S 3 4 IED S Integrated Elevator Drive System Wiring Diagram 01 System Configuration...
Страница 32: ...Chapter 3 Wiring IED S 3 7...
Страница 35: ...Chapter 3 Wiring IED S 3 10 3 3 Related Wiring Diagrams 03 Main Circuit for Drive Control Synchronous...
Страница 36: ...Chapter 3 Wiring IED S 3 11 04 Main Circuit for Drive Control Asynchronous...
Страница 38: ...Chapter 3 Wiring IED S 3 13 06 Safety Hatch...
Страница 39: ...Chapter 3 Wiring IED S 3 14 07 Brake Circuit...
Страница 40: ...Chapter 3 Wiring IED S 3 15 08 Inspection Circuit Cartop Inspection Connected to IED S Control Board...
Страница 42: ...Chapter 3 Wiring IED S 3 17 10 Input Contacts of Main Control Board for the Control Panel...
Страница 43: ...Chapter 3 Wiring IED S 3 18 11 Output Contacts of Main Control Board for the Control Panel...
Страница 44: ...Chapter 3 Wiring IED S 3 19 12 Contacts of Cartop Board OCB...
Страница 45: ...Chapter 3 Wiring IED S 3 20 13 Maneuvering Box 1 16 Floor ICB...
Страница 46: ...Chapter 3 Wiring IED S 3 21 14 1 Hall Call System...
Страница 50: ...Chapter 3 Wiring IED S 3 25 15 Lighting Circuit...
Страница 51: ...Chapter 3 Wiring IED S 3 26 16 UCMP Board Three Sensors DZU FL1 and DZD...
Страница 52: ...Chapter 3 Wiring IED S 3 27 17 UCMP Board Four Sensors DZU FL1 FL2 and DZD...
Страница 66: ...Chapter 5 Control Terminals IED S 5 1 Chapter 5 Control Terminals 5 1 Control Terminal Specifications...
Страница 67: ...Chapter 5 Control Terminals IED S 5 2 5 1 Control Terminal Specifications...
Страница 73: ...Chapter 5 Control Terminals IED S 5 8 The page intentionally left blank...
Страница 115: ...Chapter 6 Optional Accessories IED S 6 42 EMC Filter Model No B84143D0075R127 B84143D0090R127 Unit mm inch...
Страница 116: ...Chapter 6 Optional Accessories IED S 6 43 EMC Filter Model No B84143D0150R127 Unit mm inch...
Страница 117: ...Chapter 6 Optional Accessories IED S 6 44 EMC Filter Model No B84143D0200R127 Unit mm inch...
Страница 118: ...Chapter 6 Optional Accessories IED S 6 45 EMC Filter Model No B84142A0042R122 Unit mm inch...
Страница 123: ...Chapter 6 Optional Accessories IED S 6 50 The page intentionally left blank...
Страница 143: ...Chapter 7 Option Cards IED S 7 20 The page intentionally left blank...
Страница 151: ...Chapter 9 Digital Keypad IED S 9 4 Keypad Operation Process...
Страница 176: ...Chapter 10 Auto tuning Process IED S 10 9 10 3 2 Default Settings for Output Contacts of IED S Main Control Board...
Страница 177: ...Chapter 10 Auto tuning Process IED S 10 10 10 3 3 Default Settings for Contacts of IED S Cartop Board...
Страница 201: ...Chapter 10 Auto tuning Process IED S 10 34 The page intentionally left blank...
Страница 249: ...Chapter 11 Summary of Parameter Settings IED S 11 48 The page intentionally left blank...
Страница 263: ...Chapter 12 Descriptions of Parameter Settings IED S 12 00 14 The page intentionally left blank...
Страница 273: ...Chapter 12 Descriptions of Parameter Settings IED S 12 01 10 The page intentionally left blank...
Страница 281: ...Chapter 12 Descriptions of Parameter Settings IED S 12 02 8 The page intentionally left blank...
Страница 307: ...Chapter 12 Descriptions of Parameter Settings IED S 12 05 6 The page intentionally left blank...
Страница 319: ...Chapter 12 Descriptions of Parameter Settings IED S 12 06 12 The page intentionally left blank...
Страница 325: ...Chapter 12 Descriptions of Parameter Settings IED S 12 07 6 The page intentionally left blank...
Страница 345: ...Chapter 12 Descriptions of Parameter Settings IED S 12 10 8 The page intentionally left blank...
Страница 349: ...Chapter 12 Descriptions of Parameter Settings IED S 12 11 4 The page intentionally left blank...
Страница 359: ...Chapter 12 Descriptions of Parameter Settings IED S 12 12 10 The page intentionally left blank...
Страница 375: ...Chapter 12 Descriptions of Parameter Settings IED S 12 13 16 The page intentionally left blank...
Страница 381: ...Chapter 13 Warning Codes IED S 13 6 The page intentionally left blank...
Страница 415: ...Appendix A Single phase Application IED S A 4 The page intentionally left blank...
Страница 417: ...Appendix B Revision History IED S B 2 The page intentionally left blank...